Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: OHIO POWER COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of OHIO POWER COMPANY in STATE ROUTE 2, MOUNDSVILLE, WV 26041 (NAICS 221112). OSHA activity number 313370751.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ohio Power Company — free Get an email when a new federal OSHA severe-injury report for Ohio Power Company is published. One employer, no account, unsubscribe in one click.
Establishment
OHIO POWER COMPANY
Site address
STATE ROUTE 2
City
MOUNDSVILLE
State
WV
ZIP
26041
Mailing
P.O. BOX K, MOUNDSVILLE, WV 26041
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221112
SIC code (legacy)
4911
Employees
120
Ownership type
A

4 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Mar 25, 2010
Abate by
May 11, 2010
Penalty
Initial $7,000 · Current $7,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not
furnish employment and a place of employment which were free from
recognized hazards
that were likely to cause death or serious physical harm to the employees
in that employees
were exposed to fire, and/or explosion from the buildup and ignition of
flammable gas:
(a)High Sulfur Tunnel, HRC1: Employees entered the reclaim tunnel on a
regular
basis to perform maintenance such as check hoppers, grease rollers, and to
wash down coal dust accumulations.  The methane detectors in the reclaim
tunnel were not installed in close proximity to the ceiling for the
detection of
gases lighter then air exposing employees to fire and explosion of a
flammable
gas, as determined on 02/26/2010.
NOTE: Among other methods, one or more feasible and acceptable abatement
method to
prevent this hazard is to; 1) Install sensors to within one foot of the
ceiling
in the feeder
bays, 2) Install sensor to within one foot of the ceiling in the transfer
station/sump area
ceiling, 3) Provide additional ventilation in the feeder bays and transfer
station/sump areas,
and 4) Install methane detectors in the ventilation duct.
ABATEMENT CERTIFICATION REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $7000.00
  • — Z (S) $7000.00

1910.269 V11 XIC

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Mar 25, 2010
Abate by
May 11, 2010
Penalty
Initial $7,000 · Current $7,000
Recent events (2)
  • — I (S) $7000.00
  • — Z (S) $7000.00

5(a)(1)

Serious Gravity 10 1 instance 4 exposed
Issued
Mar 25, 2010
Abate by
May 11, 2010
Penalty
Initial $7,000 · Current $7,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not
furnish employment and a place of employment which were free from
recognized hazards
that were likely to cause death or serious physical harm to the employees
in that employees
were exposed to fire, and/or explosion from the buildup and ignition of
flammable gas:
(a)High Sulfur Tunnel, HRC1: Employees entered the reclaim tunnel on a
regular
basis to perform maintenance such as check hoppers, grease rollers, and to
wash down coal dust accumulations.  The methane detectors in the reclaim
tunnel were not installed in close proximity to the ceiling for the
detection of
gases lighter then air exposing employees to fire and explosion of a
flammable
gas, as determined on 02/26/2010.
NOTE: Among other methods, one or more feasible and acceptable abatement
method to
prevent this hazard is to; 1) Install sensors to within one foot of the
ceiling in the feeder
bays, 2) Install sensor to within one foot of the ceiling in the transfer
station/sump area
ceiling, 3) Provide additional ventilation in the feeder bays and transfer
station/sump areas,
and 4) Install methane detectors in the ventilation duct.
ABATEMENT CERTIFICATION REQUIRED FOR THIS ITEM
Recent events (2)
  • — I (S) $7000.00
  • — Z (S) $7000.00

1910.269 V11 XIC

Serious Gravity 10 1 instance 4 exposed
Issued
Mar 25, 2010
Abate by
May 11, 2010
Penalty
Initial $7,000
Recent events (2)
  • — I (S)
  • — Z (S) $7000.00

View Ohio Power Company's full OSHA safety record →