Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RCS SYSTEMS, INC.

Follow-up inspection · Health discipline

On , OSHA opened a follow-up health inspection of RCS SYSTEMS, INC. in 7075 W. PARKLAND CT., MILWAUKEE, WI 53223 (NAICS 337215). OSHA activity number 313524514.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch RCS Systems, INC. — free Get an email when a new federal OSHA severe-injury report for RCS Systems, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
RCS SYSTEMS, INC.
Site address
7075 W. PARKLAND CT.
City
MILWAUKEE
State
WI
ZIP
53223
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337215
SIC code (legacy)
2541
Employees
70
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Other-than-serious Gravity 02 1 instance 22 exposed
Issued
Feb 11, 2010
Abate by
Jul 29, 2011
Penalty
Initial $700
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish
employment and a place of employment which were free from recognized
hazards that were
causing or likely to cause death or serious physical harm to employees in
that employees were
exposed to wood dust explosion, deflagration or other fire hazards:
(a)The Torit/Donaldson model 276 RFW 10 dust collector, used to collect
combustible wood dust, did not have a means to prevent a fire in the dust
collector from traveling upstream or downstream (via air recirculation)
into the
plant.
Feasible abatement methods include complying with Chapter 8 of NFPA 664
Standard for the
Prevention of Fires and Explosions in Wood Processing and Woodworking
Facilities, such as
but not limited to:  (1) installing spark detection equipment and abort
gates in conformance with
NFPA 72 National Fire Alarm Code in order to divert any burning material
to atmosphere
before it can enter the plant; and (2) install isolation devices to
prevent
propagation of fire and
deflagration both upstream and downstream into the plant from the dust
collector.  Commonly
used isolation devices include abort gates, slide gates, back blast
dampers, and flame front
extinguishers.
Certification, with date and method of abatement required.
Certification of abatement is required by 29 CFR Part 1903 and is to be
submitted within ten (10)
calendar days after the abatement date.ment
Recent events (3)
  • — P (O)
  • — I (O)
  • — Z (S) $700.00

View RCS Systems, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 313524514.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.