SAFETY HARBOR, FL —
OSHA Inspection: FIRMENICH INCORPORATED
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FIRMENICH INCORPORATED in 1585 S. 10TH ST., SAFETY HARBOR, FL 34695 (NAICS 311999). OSHA activity number 313890105.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FIRMENICH INCORPORATED
- Site address
- 1585 S. 10TH ST.
- City
- SAFETY HARBOR
- State
- FL
- ZIP
- 34695
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311999
- SIC code (legacy)
- 2087
- Employees
- 43
- Ownership type
- A
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Nov 2, 2009
- Abate by
- Dec 5, 2009
- Penalty
- Initial $1,875 · Current $1,406 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and explosion hazards: a.)Sifter Room - The room was not provided with explosion relief panels, on or about September 30, 2009. b.)Sifter Room - There was 2" diameter flexible ducting connected to 4" flexible ducting that was not grounded and bonded to present static electric build-up, on or about October 29, 2009. c.)Outside of the Packaging Room - The Donaldson-Torit dust collector had deflagration venting that vented into a potentially occupied area that contained mechanical and electrical equipment, on or about October 16, 2009. ONE FEASIBLE AND ACCEPTABLE METHOD TO CORRECT THESE HAZARDS IS TO INSTITUTE A WRITTEN HOUSEKEEPING PROGRAM THAT MAINTAINS COMBUSTIBLE DUST LEVELS TO LESS THAN 1/32" ON ALL SURFACES, GROUND AND BOND ALL DUCTWORK AND LOCATE THE DUST COLLECTOR DEFLAGRATION VENT AWAY FROM POTENTIALLY OCCUPIED AREAS IN ACCORDANCE WITH NFPA 61.
Recent events (2)
- — I (S) $1406.25
- — Z (S) $1875.00
1910.22 A01
- Issued
- Nov 2, 2009
- Abate by
- Nov 13, 2009
- Penalty
- Initial $1,875 · Current $1,406 Reduced
Recent events (2)
- — I (S) $1406.25
- — Z (S) $1875.00
More inspections at Firmenich Incorporated
View Firmenich Incorporated's full OSHA safety record →
More inspections in this industry (NAICS 311999)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 313890105.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.