Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: AIR PRODUCTS AND CHEMICALS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AIR PRODUCTS AND CHEMICALS, INC. in 102 HAYES MEMORIAL DRIVE, MARLBOROUGH, MA 01752 (NAICS 325120). OSHA activity number 314072794.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AIR Products and Chemicals, INC. for free Get an email when a new federal OSHA severe-injury report for AIR Products and Chemicals, INC. is published. One employer, no account, unsubscribe in one click.
Site address
102 HAYES MEMORIAL DRIVE
City
MARLBOROUGH
State
MA
ZIP
01752
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (N)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325120
SIC code (legacy)
2813
Employees
18000
Ownership type
Private (A)

8 citations on file for this inspection.

1910.119 E03 I

Deleted Serious Gravity 03 2 instances 1 exposed
Issued
Jun 24, 2010
Abate by
Aug 10, 2010
Penalty
Initial $2,500
29 CFR 1910.119(e)(3)(i):  The process hazard analysis did not address the
hazards of the
process:
(a) Location - Establishment:
On or about 1/27/10, the employer did not perform an analysis of their
utility systems
and their affect on a potential release.l
Recent events (2)
  • · F (S)
  • · Z (S) $2500.00

1910.119 E03 VI

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jun 24, 2010
Abate by
Aug 10, 2010
Penalty
Initial $5,000
29 CFR 1910.119(e)(3)(vi):  The process hazard analysis did not address
human factors:
(a) Location - Establishment:
On or about 1/27/10, the employer's process hazard analysis did not
address
human
factors associated with snow plowing adjacent to their covered process.
Recent events (2)
  • · F (S)
  • · Z (S) $5000.00

1910.119 J04 I

Deleted Serious Gravity 10 3 instances 1 exposed
Issued
Jun 24, 2010
Abate by
Aug 10, 2010
Penalty
Initial $5,000
29 CFR 1910.119(j)(4)(i):  Inspections and tests were not performed on
process equipment to
maintain its mechanical integrity:
(a) Location - Establishment:
On or about 1/27/10, the employer failed to perform annual mechanical
integrity
inspections of their covered process in accordance with their chosen
recognized and
generally accepted good engineering practices (National Boiler and
Inspection Code and
NFPA 55).
Recent events (2)
  • · F (S)
  • · Z (S) $5000.00

1910.307 B

Deleted Serious Gravity 03 1 instance 1 exposed
Issued
Jun 24, 2010
Abate by
Aug 10, 2010
Penalty
Initial $2,500
29 CFR 1910.307 (b): All areas designated as hazardous (classified)
locations under the Class
and Zone system and areas designated under the Class and Division system
established after
August 13, 2007 shall be properly documented. This documentation shall be
available to those
authorized to design, install, inspect, maintain, or operate electric
equipment at the location.
(a) Location - Establishment:
On or about 1/27/10, the employer did not provide documentation for their
electrical
system in their Hydrogen sampling room.
Recent events (2)
  • · F (S)
  • · Z (S) $2500.00

1910.119 D03 ID

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jun 24, 2010
Abate by
Aug 10, 2010
Penalty
Initial $5,000 · Current $1,000 Reduced
29 CFR 1910.119(d)(3)(i)(D):  Process safety information pertaining to the
equipment in the
process did not include the relief system design and design basis:
(a) Location - Establishment:
On or about 1/27/10, the employer failed to provide process safety
information pertaining
to relief system design and design basis for their secondary vent
stack.ary
Recent events (2)
  • · F (O) $1000.00
  • · Z (S) $5000.00

1910.119 E03 III

Other-than-serious Gravity 10 2 instances 1 exposed
Issued
Jun 24, 2010
Abate by
Jun 29, 2010
Penalty
Initial $5,000
29 CFR 1910.119(e)(3)(iii):  The process hazard analysis did not address
the engineering and
administrative controls applicable to the hazards and their
interrelationship, such as appropriate
application of detection methodologies to provide early warning of
releases:
(a) Location - Establishment:
On or about 1/27/10, the employer failed to have available on site process
safety
information pertaining to the relief system design and design basis for
the secondary vent
stack or to specifically identify the secondary vent stack in the process
hazard analysis.
Access to such information via electronic means will be deemed to satisfy
the
requirement for access at specific work sites (provided that the
Respondent can provide
the documents by an alternate method within 15 days of request by a
responsible OSHA
official).e
Recent events (2)
  • · F (O)
  • · Z (S) $5000.00

1910.119 J05

Other-than-serious Gravity 03 1 instance 12 exposed
Issued
Jun 24, 2010
Abate by
Aug 10, 2010
Penalty
Initial $2,500 · Current $1,500 Reduced
29 CFR 1910.119(j)(5):  The employer did not correct deficiencies in
equipment that were
outside acceptable limits (as defined by process information in 29 CFR
1910.119(d) before
further use or in a safe and timely manner:
(a) Location - Establishment:
On or about 1/27/10 the employer did not correct deficiencies in their
vessel placarding
on their liquid hydrogen tank in accordance with their chosen recognized
and generally
accepted good engineering practices (NFPA 55).A
Recent events (2)
  • · F (O) $1500.00
  • · Z (S) $2500.00

1910.119 J06 III

Other-than-serious Gravity 10 2 instances 1 exposed
Issued
Jun 24, 2010
Abate by
Aug 10, 2010
Penalty
Initial $5,000 · Current $2,000 Reduced
29 CFR 1910.119(j)(6)(iii):  The employer did not assure that maintenance
materials, spare parts
and equipment were suitable for the process application for which they
were used:
(a) Location - Establishment:
On or about 1/27/10, the employer was not assuring that hand held
equipment used to
perform maintenance and inspections were calibrated for quality,
specifically the
combustible gas meter was not calibrated annually.d
Recent events (2)
  • · F (O) $2000.00
  • · Z (S) $5000.00

View AIR Products and Chemicals, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 314072794.