Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: INFRASTRUCTURE TECHNOLOGY SERVICES, INC.

Accident-driven inspection · Health discipline

On , OSHA opened an accident-driven health inspection of INFRASTRUCTURE TECHNOLOGY SERVICES, INC. in WEAVER DAIRY RD. & SHULTZ ST., CHAPEL HILL, NC 27514 (NAICS 237120). OSHA activity number 314379223.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Infrastructure Technology Services, INC. — free Get an email when a new federal OSHA severe-injury report for Infrastructure Technology Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
WEAVER DAIRY RD. & SHULTZ ST.
City
CHAPEL HILL
State
NC
ZIP
27514
Mailing
3041 BERKS WAY, STE. 102, RALEIGH, NC 27614
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237120
SIC code (legacy)
1623
Employees
6
Ownership type
A
Industry flags
Construction health.

2 citations on file for this inspection.

95012901

Serious 1 instance 2 exposed
Issued
Aug 2, 2011
Abate by
Aug 5, 2011
Penalty
Initial $2,500 · Current $1,750 Reduced
North Carolina General Statute 95-129(1) of the Occupational Safety and
Health Act of North Carolina:  The
employer did not furnish to each of his employees  conditions of
employment and a place of employment free
from recognized hazards that were causing or likely to cause death or
serious physical harm to employees, in
that employees were exposed to flash fire burns:
a)job site - on or about February 21, 2011 at approximately 4:37 P.M.,
where two employees
were utilizing a 20 lb propane torch to heat shrink anti-corrosion pipe
wrapping on 4" steel
piping, the employer failed to remove all sources of ignition at the end
of a gas piping system
in which residual gas was being purged with compressed air.
Reference: [NFPA 54 Chapter 7.3.3 (2002 Version): The open end of piping
systems being
purged shall not discharge into confined spaces or areas where there are
sources of ignition
unless precautions are taken to perform this operation in a safe manner by
ventilation of the
space, control of purging rate, and elimination of all hazardous
conditions.]
Abatement Note: One means of abatement to correct this hazard would be
remove all sources of
ignition at the discharge end of the gas line to be purged.
Recent events (2)
  • — F (S) $1750.00
  • — Z (S) $2500.00

95012901

Deleted Serious 1 instance 5 exposed
Issued
Aug 2, 2011
Abate by
Aug 5, 2011
Penalty
Initial $3,500
North Carolina General Statute 95-129(1) of the Occupational Safety and
Health Act of North Carolina:  The
employer did not furnish to each of his employees  conditions of
employment and a place of employment free
from recognized hazards that were causing or likely to cause death or
serious physical harm to employees, in
that employees were exposed to flash fire burns:
a)job site, hole #2 - where two employees were utilizing a 20 lb propane
torch to heat shrink anti-corrosion pipe wrapping on 4" steel piping, the
employer failed to displace natural gas
remaining in the gas pipe line with an inert gas, in that the gas line was
purged with compressed
air.
Reference: [NFPA 54 Chapter 7.3.1 (2002 Version): When gas piping is to be
opened for an
addition, a modification, or for service, the section to be worked on
shall be turned off from the
gas supply at the nearest convenient point and the line pressure vented to
the outdoors or to
ventilated areas of sufficient size to prevent accumulation of flammable
mixtures.  The
remaining gas in this section of pipe shall be displaced with an inert gas
as required by Table
7.3.1.]
Abatement Note: One means of abatement to correct this hazard would be to
displace any
remaining gas in the pipe with an inert gas prior to starting work.
Recent events (2)
  • — Y (S)
  • — Z (S) $3500.00

View Infrastructure Technology Services, INC.'s full OSHA safety record →