OSHA Inspection: NSTAR ELECTRIC & GAS CORP.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NSTAR ELECTRIC & GAS CORP. in 173 ALFORD STREET, EVERETT, MA 02149 (NAICS 221121). OSHA activity number 314605288.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nstar Electric & GAS Corp. — free Get an email when a new federal OSHA severe-injury report for Nstar Electric & GAS Corp. is published. One employer, no account, unsubscribe in one click.
Site address
173 ALFORD STREET
City
EVERETT
State
MA
ZIP
02149
Mailing
ONE NSTAR WAY, SE-110, WESTWOOD, MA 02090
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221121
SIC code (legacy)
4911
Employees
1000
Ownership type
A

5 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 2 instances 2 exposed
Issued
Nov 30, 2010
Abate by
Dec 3, 2010
Penalty
Initial $7,000 · Current $7,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to:
(a) Location - 173 Alford Street, Everett, MA (Station #250):
On or about 06/24/2010, employees were exposed to the hazard of electrical
shock and
burns while working with electrical equipment (current transformers) which
were not
adequately grounded.
A feasible means of abatement would have been to conform to either the
National
Electrical Safety Code (ANSI C-2) section #15 - 150 or the IEEE Guide for
Grounding
of Instrument Transformer Secondary Circuits and Cases (ANSI C57)
section(s)# 5.5.2
and 5.7.3.1.
Recent events (2)
  • — F (S) $7000.00
  • — Z (S) $7000.00

1910.269 U01

Deleted Serious Gravity 10 2 instances 2 exposed
Issued
Nov 30, 2010
Abate by
Dec 3, 2010
Penalty
Initial $7,000
Recent events (2)
  • — F (S)
  • — Z (S) $7000.00

1910.269 L02

Other-than-serious Gravity 10 2 instances 2 exposed
Issued
Nov 30, 2010
Abate by
Dec 3, 2010
Penalty
Initial $7,000 · Current $4,900 Reduced
Recent events (2)
  • — F (O) $4900.00
  • — Z (S) $7000.00

1910.303 B07 IV

Other-than-serious Gravity 05 2 instances 2 exposed
Issued
Nov 30, 2010
Abate by
Dec 3, 2010
Penalty
Initial $2,000 · Current $2,500
Recent events (2)
  • — F (O) $2500.00
  • — Z (S) $2000.00

1910.304 G05

Other-than-serious Gravity 05 2 instances 2 exposed
Issued
Nov 30, 2010
Abate by
Dec 3, 2010
Penalty
Initial $2,500
Recent events (2)
  • — F (O)
  • — Z (S) $2500.00

View Nstar Electric & GAS Corp.'s full OSHA safety record →