EVERETT, MA —
OSHA Inspection: NSTAR ELECTRIC & GAS CORP.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NSTAR ELECTRIC & GAS CORP. in 173 ALFORD STREET, EVERETT, MA 02149 (NAICS 221121). OSHA activity number 314605288.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NSTAR ELECTRIC & GAS CORP.
- Site address
- 173 ALFORD STREET
- City
- EVERETT
- State
- MA
- ZIP
- 02149
- Mailing
- ONE NSTAR WAY, SE-110, WESTWOOD, MA 02090
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221121
- SIC code (legacy)
- 4911
- Employees
- 1000
- Ownership type
- A
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Nov 30, 2010
- Abate by
- Dec 3, 2010
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: (a) Location - 173 Alford Street, Everett, MA (Station #250): On or about 06/24/2010, employees were exposed to the hazard of electrical shock and burns while working with electrical equipment (current transformers) which were not adequately grounded. A feasible means of abatement would have been to conform to either the National Electrical Safety Code (ANSI C-2) section #15 - 150 or the IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases (ANSI C57) section(s)# 5.5.2 and 5.7.3.1.
Recent events (2)
- — F (S) $7000.00
- — Z (S) $7000.00
1910.269 U01
- Issued
- Nov 30, 2010
- Abate by
- Dec 3, 2010
- Penalty
- Initial $7,000
Recent events (2)
- — F (S)
- — Z (S) $7000.00
1910.269 L02
- Issued
- Nov 30, 2010
- Abate by
- Dec 3, 2010
- Penalty
- Initial $7,000 · Current $4,900 Reduced
Recent events (2)
- — F (O) $4900.00
- — Z (S) $7000.00
1910.303 B07 IV
- Issued
- Nov 30, 2010
- Abate by
- Dec 3, 2010
- Penalty
- Initial $2,000 · Current $2,500
Recent events (2)
- — F (O) $2500.00
- — Z (S) $2000.00
1910.304 G05
- Issued
- Nov 30, 2010
- Abate by
- Dec 3, 2010
- Penalty
- Initial $2,500
Recent events (2)
- — F (O)
- — Z (S) $2500.00
More inspections at Nstar Electric & GAS Corp.
View Nstar Electric & GAS Corp.'s full OSHA safety record →