Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SUNSHINE STATE DAIRY FARMS, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SUNSHINE STATE DAIRY FARMS, LLC in 3304 SYDNEY RD., PLANT CITY, FL 33566 (NAICS 311511). OSHA activity number 314705997.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sunshine State Dairy Farms, LLC — free Get an email when a new federal OSHA severe-injury report for Sunshine State Dairy Farms, LLC is published. One employer, no account, unsubscribe in one click.
Site address
3304 SYDNEY RD.
City
PLANT CITY
State
FL
ZIP
33566
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311511
SIC code (legacy)
2026
Employees
113
Ownership type
A
Industry flags
Manufacturing safety.

3 citations on file for this inspection.

1910.119 D03 II

Serious Gravity 05 1 instance 60 exposed
Issued
Dec 1, 2010
Abate by
Apr 4, 2011
Penalty
Initial $1,625 · Current $1,138 Reduced
29 CFR 1910.119(d)(3)(ii):  The employer did not document that the
equipment in the process
complied with recognized and generally accepted good engineering practices:
a. At the site, a refrigeration system consisting of 12 compressors was
used where
ammonia was in a quantity over 10,000. The employer did not establish and
document
that the ventilation system complied with recognized and generally
accepted good
engineering practices and that it would adequately handle and exhaust
ammonia releases
from the machine room.
Recent events (2)
  • — I (S) $1137.50
  • — Z (S) $1625.00

1910.119 J02

Serious Gravity 10 4 instances 60 exposed
Issued
Dec 1, 2010
Abate by
Apr 4, 2011
Penalty
Initial $4,500 · Current $3,150 Reduced
29 CFR 1910.119(j)(2):  The employer did not establish and implement
written procedures to
maintain the on-going mechanical integrity of process equipment:
a. At the site, for the maintenance of a refrigeration system consisting
of 12 compressors where
ammonia is used in a quantity over 10,000. The employer's mechanical
integrity program was
deficient in the following:
1. Procedures were not developed and implemented to address the increase
of inspection
frequency for process equipment. The Inspection Testing and Preventive
Maintenance
program for equipment did not establish the criteria for increasing the
frequency of the
inspections and testing conducted.
2. Procedures were not developed and implemented to address the
maintenance of the
hydraulic control systems, such as but not limited to, the hydraulic
controlled valves and
slides which in turn control the level of functioning of the compressor.
3. Procedures were not developed and implemented for the calibration of
testing
equipment, such as but not limited to, the portable gauges and
thermometers. An IR heat
gun is used to establish the temperature of switches on compressors where
no calibration
procedures were developed and implemented for the testing equipment.
4. A program with procedures was not developed and implemented for
inspecting of
insulated piping. The Mechanical Integrity program does not address how to
inspect
piping under insulation.
Recent events (2)
  • — I (S) $3150.00
  • — Z (S) $4500.00

1910.119 J04 IV

Serious Gravity 05 1 instance 60 exposed
Issued
Dec 1, 2010
Abate by
Apr 4, 2011
Penalty
Initial $1,625 · Current $1,138 Reduced
29 CFR 1910.119(j)(4)(iv):  The documentation of the inspection or test
that been performed on
process equipment to maintain its mechanical integrity did not identify
the date of the inspection
or test, the serial number or other identifier of the equipment on which
the inspection or test was
performed, a description of the inspection or test, and the results of the
inspection or test:
a. At the site, Inspection Testing and Preventive Maintenance conducted
for the 12
compressors was not identified as equipment specific. Maintenance
activities and
documentation maintained did not reflect each compressor individually by
having all
required information including the identity of the equipment.
Recent events (2)
  • — I (S) $1137.50
  • — Z (S) $1625.00

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 314705997.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.