OSHA Inspection: AKZO NOBEL SURFACE CHEMISTRY, LLC

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of AKZO NOBEL SURFACE CHEMISTRY, LLC in 8005 NORTH TABLER ROAD, MORRIS, IL 60450 (NAICS 325199). OSHA activity number 315239087.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Akzo Nobel Surface Chemistry, LLC — free Get an email when a new federal OSHA severe-injury report for Akzo Nobel Surface Chemistry, LLC is published. One employer, no account, unsubscribe in one click.
Site address
8005 NORTH TABLER ROAD
City
MORRIS
State
IL
ZIP
60450
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325199
SIC code (legacy)
2869
Employees
100
Ownership type
A

13 citations on file for this inspection.

1910.119 D03 ID

Serious Gravity 10 7 instances 100 exposed
Issued
Nov 1, 2011
Abate by
Nov 4, 2011
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.119(d)(3)(i)(D):  Process safety information pertaining to the
equipment in the
process did not include the relief system design and design basis:
Akzo Nobel Surface Chemistry, LLC., did not include the design basis for
the following
safety valves in the process safety information for the Arquad Unit
Reactor #1:
a. PSV 309-310
b. PSV 309-401
c. PSV 309-410
d. PSV 309-411
e. PSV 309-413
f. PSV 309-425
g. PSV 309-426
THIS ITEM CORRECTED DURING INSPECTION
Recent events (2)
  • — I (S) $4900.00
  • — Z (S) $7000.00

1910.119 E01

Serious Gravity 10 1 instance 100 exposed
Issued
Nov 1, 2011
Abate by
Apr 1, 2012
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.119(e)(1):  The employer did not perform an initial process
hazard analysis
(hazard evaluation) on processes covered by 29 CFR 1910.119:
In May, 2010, a hydrogen storage tank, with a capacity of 10,000 pounds,
was installed
at the Akzo Nobel Surface Chemistry, LLC, Morris, Illinois plant.  The
employer did
not perform an initial process hazard analysis on the Hydrogen Storage and
Transfer
Unit.
DOCUMENTATION AND CERTIFICATION IS REQUIRED FOR THIS ITEM.
Recent events (2)
  • — I (S) $4900.00
  • — Z (S) $7000.00

1910.119 F01 IIB

Serious Gravity 10 1 instance 100 exposed
Issued
Nov 1, 2011
Abate by
Nov 4, 2011
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.119(f)(1)(ii)(B):  The employer's written operating procedures
covering the
operating limits did not address the steps required to correct or avoid
deviation beyond such
operating limits:
The operating procedures for the Arquad Unit Reactor #1, at the Akzo Nobel
Surface
Chemistry, LLC plant in Morris, Illinois, did not address the steps
required to correct
or avoid deviations from the normal operating limits such as
over-pressurization
or over-
charging of the reactor.
THIS ITEM WAS CORRECTED DURING THE INSPECTION
Recent events (2)
  • — I (S) $4900.00
  • — Z (S) $7000.00

1910.119 J04 I

Deleted Serious Gravity 10 6 instances 100 exposed
Issued
Nov 1, 2011
Abate by
Feb 1, 2012
Penalty
Initial $7,000
29 CFR 1910.119(j)(4)(i):  Inspections and tests were not performed on
process equipment to
maintain its mechanical integrity:
The following equipment, at Akzo Nobel Surface Chemistry, LLC, in Morris,
Illinois,
has not been inspected or tested in order to maintain its mechanical
integrity:
a. East Batch Hydro Ammonia Feed Pump (389-125.1)
b. West Batch Hydro Ammonia Feed Pump (389-126.1)
c. Wash Tank Scrubber Pump (309-171)
d. Continuous Hydro Ammonia Feed Pump (303-014.2)
e. Ammonia Unloading Pump (389-632)
f. The gaskets on the baffle flanges on the Arquad Reactor #2.
DOCUMENTATION AND CERTIFICATION IS REQUIRED FOR THIS ITEM.
Recent events (2)
  • — I (S)
  • — Z (S) $7000.00

1910.119 J04 II

Deleted Serious Gravity 10 3 instances 100 exposed
Issued
Nov 1, 2011
Abate by
Feb 1, 2012
Penalty
Initial $7,000
29 CFR 1910.119(j)(4)(ii):  Inspections and testing procedures performed
on process equipment
to maintain its mechanical integrity, did not follow recognized and
generally accepted good
engineering practices:
Inspections on the following equipment, at Akzo Nobel Surface Chemistry,
LLC, in
Morris, Illinois, did not follow recognized and generally accepted good
engineering
practices:
a.The results of the piping inspections for Arquad Unit Reactor #1 and the
Ammonia Storage and Transfer Unit are not reviewed by an Authorized
Piping Inspector who has received certification in accordance with API
570 Piping Inspections Code: In-Service Inspection, Rating, Repair, and
Alteration of Piping Systems, November, 2009.
b.The results of the pressure vessel inspections for Arquad Unit Reactor #1
and the Ammonia Storage and Transfer Unit are not reviewed by a
Certified Inspector in accordance with API 510 Pressure Vessel Inspection
Code: In-Service Inspection, Rating, Repair and Alteration, June, 2006.
c.Arquad Unit Reactor #1: The corrosion rates have not been identified or
calculated for this vessel in accordance with API 510 Pressure Vessel
Inspection Code: In-Service Inspection, Rating, Repair and Alteration,
June, 2006.
DOCUMENTATION AND CERTIFICATION IS REQUIRED FOR THIS ITEM.
Recent events (2)
  • — I (S)
  • — Z (S) $7000.00

1910.119 J04 III

Serious Gravity 10 3 instances 100 exposed
Issued
Nov 1, 2011
Abate by
Jun 1, 2012
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.119(j)(4)(iii):  The frequency of inspections and tests of
process equipment to
maintain its mechanical integrity, was not consistent with applicable
manufacturers'
recommendations and good engineering practices, or more frequently
determined to be necessary
by prior operating experience:
The frequency of inspections and test for the following equipment at Akzo
Nobel Surface
Chemistry, LLC, in Morris, Illinois, was not consistent with good
engineering practices:
a.South Alcohol Recovery Tank (309-314) has not had an internal inspection
in accordance with API 510 Pressure Vessel Inspection Code: In-Service
Inspection, Rating, Repair and Alteration, June, 2006, within the past 10
years.
b.Arquad Alcohol Chiller Wash Tank (309-410) has not had an internal
inspection in accordance with API 510 within the past 10 years.
c.North Alcohol Recovery Tank (309-315) has not had an internal inspection
in accordance with API 510 within the past 10 years.
DOCUMENTATION AND CERTIFICATION IS REQUIRED FOR THIS ITEM.
Recent events (2)
  • — I (S) $4900.00
  • — Z (S) $7000.00

1910.119 J05

Serious Gravity 10 3 instances 100 exposed
Issued
Nov 1, 2011
Abate by
Dec 31, 2012
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.119(j)(5):  The employer did not correct deficiencies in
equipment that were
outside acceptable limits (as defined by process information in 29 CFR
1910.119(d) before
further use or in a safe and timely manner:
Akzo Nobel Surface Chemistry, LLC, Morris, Illinois, did not correct the
following
deficiencies in equipment that were outside acceptable limits before
further use or in a
safe and timely manner when necessary means are taken to assure safe
operation:
a.MI-Reactor Vent Chiller (309-409): In 2008, an inspection indicated that
the top head thickness was below that which was minimally required.  No
action has been taken to address or correct this condition.  In 2008, an
inspection indicated that the shell was too corroded and pitted to take any
readings.  No action has been taken to address or correct this condition.
b.Arquad Drop Tank Reboiler (309-414): In 1998, all head readings were
well below the minimum thickness required.  No action has been taken to
address or correct this condition.
c.Alcohol/MeCl Chiller (309-413): In 2003, shell readings were below the
minimum thickness required.  No action has been taken to address or
correct this condition.
DOCUMENTATION AND CERTIFICATION IS REQUIRED FOR THIS ITEM.
Recent events (2)
  • — I (S) $4900.00
  • — Z (S) $7000.00

1910.119 L02

Deleted Serious Gravity 10 1 instance 100 exposed
Issued
Nov 1, 2011
Abate by
Nov 4, 2011
Penalty
Initial $7,000
29 CFR 1910.119(l)(2): The written procedures did not assure that the
considerations in
subparagraphs (i) through (v) were addressed prior to any change:
Prior to the installation of bracing on spools at Arquad Unit, Reactors
#1, 2 and 3, at
Akzo Nobel Surface Chemistry, LLC, in Morris, Illinois, the considerations
of
subparagraphs (i) through (v) were not addressed.  The subparagraphs
include the
technical basis, impact of change on safety and health, modifications to
operating
procedures, necessary time period for change, and authorization
requirements for the
change.
THIS ITEM WAS CORRECTED DURING THE INSPECTION.
Recent events (2)
  • — I (S)
  • — Z (S) $7000.00

1910.119 O04

Deleted Serious Gravity 10 1 instance 100 exposed
Issued
Nov 1, 2011
Abate by
Feb 1, 2012
Penalty
Initial $7,000
29 CFR 1910.119(o)(4):  The employer did not determine and document an
appropriate response
to each of the findings of the compliance audit required by 29 CFR
1910.119(o)(1), and
document that the deficiencies had been corrected:
In 2008, a psm audit was conducted at Akzo Nobel Surface Chemistry, LLC,
in Morris,
Illinois.  One of the action items, Item PSI-1-R, was closed out prior to
the completion
of the actual work to correct the deficiency.
DOCUMENTATION AND CERTIFICATION IS REQUIRED FOR THIS ITEM.
Recent events (2)
  • — I (S)
  • — Z (S) $7000.00

1910.119 J04 I

Serious Gravity 10 6 instances 100 exposed
Issued
Nov 1, 2011
Abate by
Apr 1, 2012
Penalty
Current $4,900
Recent events (3)
  • — Q $7000.00
  • — I (S) $4900.00
  • — Z (S) $7000.00

1910.119 J04 II

Serious Gravity 10 3 instances 100 exposed
Issued
Nov 1, 2011
Abate by
Apr 1, 2012
Recent events (3)
  • — Q $7000.00
  • — I (S)
  • — Z (S) $7000.00

1910.119 L02

Serious Gravity 10 1 instance 100 exposed
Issued
Nov 1, 2011
Abate by
Nov 4, 2011
Penalty
Current $4,900
Recent events (3)
  • — Q $7000.00
  • — I (S) $4900.00
  • — Z (S) $7000.00

1910.119 O04

Serious Gravity 10 1 instance 100 exposed
Issued
Nov 1, 2011
Abate by
Apr 1, 2012
Recent events (3)
  • — Q $7000.00
  • — I (S)
  • — Z (S) $7000.00

View Akzo Nobel Surface Chemistry, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 315239087.