LEWISTON, ME —
OSHA Inspection: WALMART GROCERY DISTRIBUTION CENTER #7014
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WALMART GROCERY DISTRIBUTION CENTER #7014 in 31 ALFRED PLOURDE PARKWAY, LEWISTON, ME 04240 (NAICS 493120). OSHA activity number 315285080.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WALMART GROCERY DISTRIBUTION CENTER #7014
- Site address
- 31 ALFRED PLOURDE PARKWAY
- City
- LEWISTON
- State
- ME
- ZIP
- 04240
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- SIC code (legacy)
- 4222
- Employees
- 580
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 F01 IIIB
- Issued
- Jun 30, 2011
- Abate by
- Aug 5, 2011
General-duty citation text
29 CFR 1910.119(f)(1)(iii)(B): The employer's written operating procedures covering safety and health considerations did not address the precautions necessary to prevent exposure, including engineering controls, administrative controls, and person protective equipment: Establishment - Written procedures for removing oil from the refrigeration process equipment did not specify the personal protective equipment to be used.
Recent events (2)
- — F (O)
- — Z (O)
1910.119 J02
- Issued
- Jun 30, 2011
- Abate by
- Aug 5, 2011
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going mechanical integrity of process equipment: Establishment - The employer did not ensure that written procedures were maintained for annual testing of the high discharge-temperature/low suction pressure and high-discharge pressure limiting devices on the eight refrigeration system compressors.n
Recent events (2)
- — F (O)
- — Z (O)
1910.119 J04 IV
- Issued
- Jun 30, 2011
- Abate by
- Aug 5, 2011
General-duty citation text
29 CFR 1910.119(j)(4)(iv): The employer did not document each inspection and test that had been performed on process equipment to maintain its mechanical integrity: Establishment - The employer did not ensure that annual testing of the high discharge- temperature/low suction pressure and high-discharge pressure limiting devices on the eight refrigeration system compressors was documented.
Recent events (2)
- — F (O)
- — Z (O)
1910.119 L01
- Issued
- Jun 30, 2011
- Abate by
- Jul 5, 2011
General-duty citation text
29 CFR 1910.119(l)(1): The employer did not establish and implement written procedures to manage changes to process chemicals, technology, equipment, and procedures; and, changes to facilities that affect a covered process: Establishment - The management of change documentation associated with the relocation of the Hot Gas King Valve was not available.
Recent events (2)
- — F (O)
- — Z (O)
More inspections at Walmart Grocery Distribution Center #7014
View Walmart Grocery Distribution Center #7014's full OSHA safety record →
More inspections in this industry (NAICS 493120)
More inspections in ME
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 315285080.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.