Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: THE PORK COMPANY

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of THE PORK COMPANY in 892 PENNY BRANCH ROAD, WARSAW, NC 28398 (NAICS 311611). OSHA activity number 315452623.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Pork Company — free Get an email when a new federal OSHA severe-injury report for The Pork Company is published. One employer, no account, unsubscribe in one click.
Establishment
THE PORK COMPANY
Site address
892 PENNY BRANCH ROAD
City
WARSAW
State
NC
ZIP
28398
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311611
SIC code (legacy)
2011
Employees
160
Ownership type
A
Industry flags
Manufacturing health.

7 citations on file for this inspection.

95012901

Serious 1 instance 6 exposed
Issued
Dec 2, 2011
Abate by
Dec 29, 2011
Penalty
Initial $4,200 · Current $4,200
North Carolina General Statute 95-129(1) of the Occupational Safety and
Health Act of North Carolina:  The
employer did not furnish each of his employees conditions of employment
and a place of employment free from
recognized hazards that were causing or likely to cause death or serious
physical harm to employees in that
employees were exposed to Freon, R-22:
a)facility, freon room - where the employer did not post emergency
shutdown procedures for
maintenance employees who conducted routine inspections on refrigeration
systems containing
R-22 Freon, and are subject to an uncontrolled release of this chemical.
One feasible and acceptable abatement method, among others, to correct
this hazard is the
following:
1.Emergency shutdown procedures, including precautions to be observed in
case of a
breakdown or leak, shall be displayed on a conspicuous card located as
near as possible
to the refrigerant compressor.  These precautions shall address:
a)instructions for shutting down the system in case of emergency;
b)the name, address, and day and night telephone numbers for obtaining
service;
and
c)the names, addresses, and telephone numbers of all corporate, local,
state, and
federal agencies to be contacted as required in the event of a reportable
incident.
Reference: ANSI/ASHRAE Standard 15-2004, Safety Standard for Refrigeration
Systems,
Section 11.7
b)facility, freon room - where the employer did not post the entrance to
the freon room
prohibiting access by unauthorized personnel.
One feasible and acceptable abatement, among others, to correct this
hazard is:
1.At the entrance to each refrigerating machinery room, provide a legible
permanent sign,
securely attached and easily accessible, reading "Machinery Room -
Authorized
Personnel Only." The sign shall further communicate that entry is
forbidden except by
those personnel trained in the emergency procedures.
Reference: ANSI/ASHRAE Standard 15-2004, Safety Standard for Refrigeration
Systems,
Section 11.2.4.
c)facility, freon room - for maintenance employees conducting routine
inspections in the freon
system, the freon room was not equipped with a detector and alarm.
One feasible and acceptable abatement, among others, to correct this
hazard is:
1.Install a detector in an area where refrigerant from a leak will
concentrate, that actuates
an alarm.
2.The alarm shall annunciate visual and audible alarms inside and outside
the freon room.
Reference: ANSI/ASHRAE Standard 15-2004, Safety Standard for Refrigeration
Systems,
Section 8.11.2.1.tion
Recent events (2)
  • — I (S) $4200.00
  • — Z (S) $4200.00

1910.1200 H03 III

Serious 1 instance 6 exposed
Issued
Dec 2, 2011
Abate by
Jan 23, 2012
Penalty
Initial $4,200
Recent events (2)
  • — I (S)
  • — Z (S) $4200.00

1910.1026 D02 I

Serious 1 instance 1 exposed
Issued
Dec 2, 2011
Abate by
Dec 7, 2011
Penalty
Initial $750 · Current $750

Hazardous substances 0685

Recent events (2)
  • — I (S) $750.00
  • — Z (S) $750.00

1910.1026 H02 II

Serious 1 instance 1 exposed
Issued
Dec 2, 2011
Abate by
Dec 7, 2011

Hazardous substances 0685

Recent events (2)
  • — I (S)
  • — Z (S)

1910.1026 H02 IV

Serious 1 instance 1 exposed
Issued
Dec 2, 2011
Abate by
Dec 7, 2011

Hazardous substances 0685

Recent events (2)
  • — I (S)
  • — Z (S)

1910.1026 H03 III

Serious 1 instance 1 exposed
Issued
Dec 2, 2011
Abate by
Dec 7, 2011
Recent events (2)
  • — I (S)
  • — Z (S)

1904.29 B03

Other-than-serious 1 instance 1 exposed
Issued
Dec 2, 2011
Abate by
Dec 7, 2011
Penalty
Initial $600 · Current $600
Recent events (2)
  • — I (O) $600.00
  • — Z (O) $600.00

View The Pork Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 315452623.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.