MUMFORD, NY —
OSHA Inspection: GRIFFITH ENERGY/SUPERIOR PLUS ENERGY SERVICES INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of GRIFFITH ENERGY/SUPERIOR PLUS ENERGY SERVICES INC. in 1104 MAIN STREET, MUMFORD, NY 14511 (NAICS 454312). OSHA activity number 315503441.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GRIFFITH ENERGY/SUPERIOR PLUS ENERGY SERVICES INC.
- Site address
- 1104 MAIN STREET
- City
- MUMFORD
- State
- NY
- ZIP
- 14511
- Mailing
- 760 BROOKS AVENUE, ROCHESTER, NY 14619
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 454312
- SIC code (legacy)
- 5984
- Employees
- 2
- Ownership type
- A
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Jan 5, 2012
- Abate by
- Feb 7, 2012
- Penalty
- Initial $7,000 · Current $3,800 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: a) On or about 9/13/11 at the Mumford facility; employees who transfer liquified petroleum gas, operate pumps, valves and hoses containing liquified petroleum gas and are involved in draining and emptying containers of liquified petroleum gas were last trained on these activities May 13, 2008. ABATEMENT DOCUMENTATION REQUIRED Section 4.4 of the 2011 National Fire Protection Associate Code 58, Liquified Petroleum Gas states: " Persons who transfer liquid LP-Gas, who are employed to transport LP- Gas, or whose primary duties fall within the scope of this code shall be trained in the proper handling procedures. Refresher training shall be provided at least every 3 years. The training shall be documented. Suggested abatement action would be to train employees involved in the transfer and operation of equipment containing liquified petroleum on the required steps to safely perform each required task or activity at least every three years.
Recent events (2)
- — I (S) $3800.00
- — Z (S) $7000.00
5(a)(1)
- Issued
- Jan 5, 2012
- Abate by
- Feb 7, 2012
- Penalty
- Initial $7,000 · Current $3,850 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: a) On or about 9/13/11 at the Mumford, New York facility; emergency shut off valves are inspected on a monthly basis as part of the site Monthly Inspection Checklist, but annual testing was not completed in 2010 or 2011. ABATEMENT DOCUMENTATION REQUIRED Section 6.12.9 of the NFPA Liquified Petroleum Gas Code, 2011 edition, requires emergency shut off valves required by the code shall be tested annually for the function required by 5.12.4 (2) and (3) and the results documented. Section 5.12.4 states: Emergency shut off valves shall be approved and shall incorporate all of the following means of closing: (2) Manual shutoff from a remote location (3) Manual shutoff from at the installed location. Note: Section 10.9 of the NFPA Liquified Petroleum Gas Code, 2004 edition, requires annual testing of emergency shut off valves. Feasible and acceptable means of abatement would be to conduct an annual test of the emergency shutoff valves and document the action of both the shutoff from a remote location and at the installed location.
Recent events (2)
- — I (S) $3850.00
- — Z (S) $7000.00
1910.132 A
- Issued
- Jan 5, 2012
- Abate by
- Feb 7, 2012
- Penalty
- Initial $7,000 · Current $3,850 Reduced
Recent events (2)
- — I (S) $3850.00
- — Z (S) $7000.00
1910.178 L04 I
- Issued
- Jan 5, 2012
- Abate by
- Feb 7, 2012
- Penalty
- Initial $4,000 · Current $2,200 Reduced
Recent events (2)
- — I (S) $2200.00
- — Z (S) $4000.00
1910.305 B01
- Issued
- Jan 5, 2012
- Abate by
- Jan 10, 2012
- Penalty
- Initial $4,000 · Current $2,200 Reduced
Recent events (2)
- — I (S) $2200.00
- — Z (S) $4000.00