BALTIMORE, MD —
OSHA Inspection: MORGAN STATE UNIVERSITY
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of MORGAN STATE UNIVERSITY in 1700 EAST COLD SPRING LANE, BALTIMORE, MD 21215 (NAICS 611310). OSHA activity number 316174242.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MORGAN STATE UNIVERSITY
- Site address
- 1700 EAST COLD SPRING LANE
- City
- BALTIMORE
- State
- MD
- ZIP
- 21215
- Mailing
- 1700 EAST COLD SPRING LANE, BALTIMORE, MD 21215
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 611310
- SIC code (legacy)
- 8221
- Employees
- 21
- Ownership type
- C
Citations
3 citations on file for this inspection.
1910.1450 E01
- Issued
- May 2, 2012
- Abate by
- Sep 1, 2012
Recent events (2)
- — P (S)
- — Z (S)
1910.1450 F01
- Issued
- May 2, 2012
- Abate by
- Sep 1, 2012
Recent events (2)
- — P (S)
- — Z (S)
50104 A
- Issued
- May 2, 2012
- Abate by
- May 10, 2012
General-duty citation text
Labor and Employment Article, Section 5-104(a): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees: (a)Date of Violation:02/24/12 Location:Chemistry Large Storeroom Condition:The hazardous chemicals observed included, but were not limited to, ammonium hydroxide, 28-30, a highly corrosive material, where four plumbed eyewashes inside the storeroom did not provide a sufficient amount of clean flushing fluid and did not provide spray heads protection from contaminants. Among other methods, a feasible and acceptable method of abatement to correct these hazards is to comply with ANSI Z358.1 which includes protecting the spray heads from airborne contaminants, ensuring that the water supply is capable of delivering clean, sufficient flow and volume of flushing fluid for the required amount of time, inspecting the eyewashes regularly to ensure that they are accessible and free of dirt and debris, and testing plumbed eyewashes regularly to ensure that the proper flow rate is maintained. Abatement documentation (photographs, receipts, copies of programs, training certification, etc.) is required for this item.
More inspections at Morgan State University
View Morgan State University's full OSHA safety record →
More inspections in this industry (NAICS 611310)
More inspections in MD
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 316174242.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.