MANASSAS, VA —
OSHA Inspection: MICRON TECHNOLOGY OF VIRGINIA
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of MICRON TECHNOLOGY OF VIRGINIA in 9600 GODWIN DRIVE, MANASSAS, VA 20109 (NAICS 334413). OSHA activity number 316313469.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MICRON TECHNOLOGY OF VIRGINIA
- Site address
- 9600 GODWIN DRIVE
- City
- MANASSAS
- State
- VA
- ZIP
- 20109
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 334413
- SIC code (legacy)
- 3674
- Employees
- 1727
- Ownership type
- A
- Industry flags
- Manufacturing health.
Citations
1 citation on file for this inspection.
510001 A
- Issued
- Mar 12, 2012
- Abate by
- Apr 14, 2012
- Penalty
- Initial $2,275
General-duty citation text
Title 40.1-51.1(a) Code of Virginia: The employer, Micron Technology Inc., did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious bodily harm to employees in that employees were exposed to hydrofluoric acid during a demolition operation. On February 9, 2012, at 9600 Godwin Drive, Manassas, Virginia, an employee of Craftcorp was working to remove an approximately 80 ft long hydrofluoric acid line. Prior to removal, it was Micron Technology Incorporated's duty to ensure that the line was properly decontaminated. Part of the decontamination process was to purge the line for at least one hour by blowing the line dry with nitrogen. According to Micron's documents, the line was not purged at all. In accordance with the MTV Equipment Decontamination and Defacilitation Form and previously established procedures for a demolition operation, it is both Micron Technology Inc. and Craftcorp's responsibility to verify that the decontamination procedures were completed. One feasible and acceptable abatement method, among others, to correct this hazard is for the employer to follow previously established procedures that ensure the decontamination process is complete.nation
Recent events (3)
- — I (S)
- — W (S) $2275.00
- — Z (S) $2275.00
More inspections at Micron Technology of Virginia
View Micron Technology of Virginia's full OSHA safety record →
More inspections in this industry (NAICS 334413)
More inspections in VA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 316313469.