Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CARRBORO HIGH SCHOOL

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of CARRBORO HIGH SCHOOL in 201 ROCK HAVEN ROAD, CARRBORO, NC 27510 (NAICS 611110). OSHA activity number 316777002.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Carrboro High School — free Get an email when a new federal OSHA severe-injury report for Carrboro High School is published. One employer, no account, unsubscribe in one click.
Site address
201 ROCK HAVEN ROAD
City
CARRBORO
State
NC
ZIP
27510
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
611110
SIC code (legacy)
8211
Employees
80
Ownership type
B
Industry flags
Manufacturing health.

1 citation on file for this inspection.

95012901

Serious 3 instances 3 exposed
Issued
Dec 14, 2012
Abate by
Jan 9, 2013
Penalty
Initial $2,100 · Current $2,100
North Carolina General Statute 95-129(1) of the Occupational Safety and
Health Act of North Carolina:  The
employer did not furnish each of his employees conditions of employment
and a place of employment free from
recognized hazards that were causing or likely to cause death or serious
physical harm to employees in that
employees were exposed to a fire hazard:
a)Room D224 - where the natural gas emergency shut off switch located on
the instructor's desk
did not function properly.  The switch did not effectively isolate the gas
supply from the
appliance(s) located on the students' desks throughout the classroom.
b)Room E214 -  where the natural gas emergency shut off switch located on
the instructor's desk
did not function properly.  The switch did not effectively isolate the gas
supply from the
appliance(s) located on the students' desks throughout the classroom.
c)Room E223 - where the natural gas emergency shut off switch located on
the instructor's desk
did not function properly.  The switch did not effectively isolate the gas
supply from the
appliance(s) located on the students' desks throughout the classroom.
Abatement Note:
Among other methods, one feasible and acceptable method to prevent this
hazard is to comply with the National
Fire Protection Association (NFPA) Standard 54-2012, the National Fuel Gas
Code.  Reference paragraph 11.3
requires, in part, that "where the (safety shutoff) device does not
function properly to turn off the gas supply in
the event of pilot outage or other improper operation, it shall be
properly serviced or replace with a new
device."