Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: URS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of URS in 97 RIVER ROAD, BOW, NH 03304 (NAICS 237130). OSHA activity number 330016700.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch URS — free Get an email when a new federal OSHA severe-injury report for URS is published. One employer, no account, unsubscribe in one click.
Establishment
URS
Site address
97 RIVER ROAD
City
BOW
State
NH
ZIP
03304
Mailing
97 RIVER ROAD, BOW, NH 03304
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
50000
Ownership type
A

3 citations on file for this inspection.

1926.21 B02

Deleted Serious Gravity 5 4 instances 5 exposed
Issued
Jul 13, 2011
Abate by
Jul 27, 2011
Penalty
Initial $3,750 · Current $0 Reduced
29 CFR 1926.21(b)(2):  The employer did not instruct each employee in the recognition and avoidance of unsafe conditions andthe regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury.  a.  Site - The employees were not adequately trained in the methods and procedures to be used when applying both danger and lockout tags.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3750

1926.200 B01

Deleted Serious Gravity 5 4 instances 1 exposed
Issued
Jul 13, 2011
Abate by
Jul 27, 2011
Penalty
Initial $0 · Current $0
29 CFR 1926.200(b)(1):   Danger signs (see Figure G-1) were not used only when an immediate hazard exists      a.  Gypsum Building motors G1A and G1B - The employer did not use a danger sign to notify employees employees that a circuit was locked in the live/closed position.  Instead the employer used a lockout/tagout device (tag) to lock the circuit in the live/closed position which could have caused an employee to understand that an energized circuit was de-energized.    b.  FDG Building Sterling Boiler temporary power panel upper level - The employer did not use a danger sign to notify employees that a circuit was locked in the live/closed position.  Instead the employer used a lockout/tagout device (tag) to lock the circuit in the live/closed position which could have caused an employee to understand that an energized circuit was de-energized.    c.  Smoke Stack FAA light control panel - The employer did not use a danger sign to notify employees that a circuit was locked in the live/closed position.  Instead the employer used a lockout/tagout device (tag) to lock the circuit in the live/closed position which could have caused an employee to understand that an energized circuit was de-energized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.34 B

Deleted Serious Gravity 1 200 exposed
Issued
Jul 13, 2011
Penalty
Initial $2,250 · Current $0 Reduced
29 CFR 1926.34(b): Exits were not marked by a readily visible sign:  (a) FGD Building - Exit doorways were not labeled.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2250

View URS's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 330016700.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.