Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SUNSHINE MINTING, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SUNSHINE MINTING, INC. in 750 CANFIELD AVE., COEUR D ALENE, ID 83815 (NAICS 332116). OSHA activity number 330017948.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sunshine Minting, INC. — free Get an email when a new federal OSHA severe-injury report for Sunshine Minting, INC. is published. One employer, no account, unsubscribe in one click.
Site address
750 CANFIELD AVE.
City
COEUR D ALENE
State
ID
ZIP
83815
Mailing
7600 MINERAL DRIVE SUITE 700, COEUR D ALENE, ID 83815
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332116
Employees
180
Ownership type
A

4 citations on file for this inspection.

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 19, 2011
Abate by
Apr 26, 2011
Penalty
Initial $6,300 · Current $3,700 Reduced
29 CFR 1910.333(a)(1):  Live parts to which an employee may be exposed were not deenergized before the employee works on or near them.      a)	Distribution Panel #3:  On or about March 22, 2011 and at times prior thereto, employees were permitted to work on the 480 volt, 3000 amp Meltroom 4 bucket without it being deenergized.    Note:  Abatement certification and supporting documentation are required for this item.
Recent events (2)
  • — I (S) $3700
  • — Z (S) $6300

1910.335 A01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 19, 2011
Abate by
Apr 26, 2011
Penalty
Initial $6,300 · Current $3,650 Reduced
29 CFR 1910.335(a)(1)(i):  Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed.    a)	Distribution Panel #3:  On or about March 22, 2011 and at times prior thereto, employees performed maintenance on the energized 480 volt, 3000 amp Meltroom 4 bucket without proper personal protective equipment.      Note:  Abatement certification and supporting documentation are required for this item.
Recent events (2)
  • — I (S) $3650
  • — Z (S) $6300

1910.335 A02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 19, 2011
Abate by
Apr 26, 2011
Penalty
Initial $6,300 · Current $3,650 Reduced
29 CFR 1910.335(a)(2)(i):  Each employee did not use insulated tools or handling equipment if the tools or handling equipment might make contact with such conductors or parts when working near exposed energized conductors or circuit parts.    a)	Distribution Panel #3:  On or about March 22, 2011 and at times prior thereto, employees performed maintenance on the energized 480 volt, 3000 amp Meltroom 4 bucket without insulated tools.    Note:  Abatement certification and supporting documentation are required for this item.
Recent events (2)
  • — I (S) $3650
  • — Z (S) $6300

1910.37 B06

Other-than-serious 2 instances 180 exposed
Issued
Apr 19, 2011
Abate by
May 10, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6):  Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color.     a)	Meltroom:  On or about March 22, 2011 and at times prior thereto, the exit sign over the meltroom door was not illuminated by a reliable light source.  The nearest emergency light was approximately 48 feet away.    b)	Packaging:  On or about March 22, 2011 and at times prior thereto, two direction exit signs were not illuminated by a reliable light source.  There was no emergency light within a line of sight of the exit signs.    Note:  Abatement certification is required for this item.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Sunshine Minting, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 330017948.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.