Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: U.S. GEOLOGICAL SURVEY - COLUMBIARIVERRESEARCHLAB

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. GEOLOGICAL SURVEY - COLUMBIARIVERRESEARCHLAB in 5501-A, COOK-UNDERWOOD RD., COOK, WA 98605 (NAICS 924120). OSHA activity number 330974726.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Geological Survey - Columbiariverresearchlab for free Get an email when a new federal OSHA severe-injury report for U.S. Geological Survey - Columbiariverresearchlab is published. One employer, no account, unsubscribe in one click.
Site address
5501-A, COOK-UNDERWOOD RD.
City
COOK
State
WA
ZIP
98605
Mailing
5501-A, COOK-UNDERWOOD RD., COOK, WA 98605
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
65
Ownership type
Federal government (D)

9 citations on file for this inspection.

1910.151 C

Serious 1 exposed
Issued
Sep 7, 2011
Abate by
Oct 20, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.151(c): \\r\\n\\r\\nWhere employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:\\r\\n\\r\\na) In the Dry Lab, workers handling hydrochloric acid were not providice an eyewash capable of being operating  hands free.
Recent events (1)
  • · Z (S) $0

1910.212 B

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 7, 2011
Abate by
Oct 20, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.212(b):  Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:    a) Boat house, woodshop, Craftsman 20 inch drill press sn/REY1001.
Recent events (1)
  • · Z (S) $0

1910.1001 J03 V

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 7, 2011
Abate by
Oct 20, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.1001(j)(3)(v): The building or facility owner did not post a sign which identified material that contained asbestos containing material (ACM) as to its location and instructions in appropriate work practices:\r\n\r\na) Second floor GIS storage room, an attic space with asbestos containing roofing shingles ,now used as flooring are exposed to occupant traffic and were being damaged without a communicating a warning or precautionary instructions.
Recent events (1)
  • · Z (S) $0

1910.1001 J07 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 7, 2011
Abate by
Oct 7, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.1001(j)(7)(iv):  The employer did not provide to all employees who perform housekeeping work in areas where ACM and PACM is present, an asbestos awareness training course covering the health effects of asbestos; and/or locations of ACM and/or recognition of ACM and PACM damage and deterioration and/or requirements in this standard related to housekeeping, and/or proper response to fiber release episodes:\r\n\r\na) In the second floor GIS storage room, asbestos containing roofing shingles were broken and laying on floor; maintenance workers were not trained to recognized hazard or clean up the broken pieces.\r\n
Recent events (1)
  • · Z (S) $0

1910.1001 K01

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 7, 2011
Abate by
Oct 20, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.1001(k)(1):  The employer did not maintain all surfaces as free as practicable of ACM waste and/or debris and accompanying dust:\r\n\r\na) In the second floor GIS storage room the attic space was littered with broken pieces of asbestos containing roofing shingles.
Recent events (1)
  • · Z (S) $0

1910.1001 K02

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 7, 2011
Abate by
Oct 7, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.1001(k)(2): All spills and sudden releases of material containing asbestos were not cleaned up as soon as possible:\r\n\r\na) In the second floor GIS storage room, the attic space was littered with broken asbestos containing roofing shingles.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Other-than-serious 1 exposed
Issued
Sep 7, 2011
Abate by
Oct 20, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): \r\n\r\nListed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:\r\n\r\na) In the dry lab the pendent outlets were made from junction boxes designed to be a stationary installation attached to a wall stud.
Recent events (1)
  • · Z (O) $0

1910.305 B02 I

Other-than-serious 1 instance 2 exposed
Issued
Sep 7, 2011
Abate by
Oct 20, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:\r\n\r\na) A wall recepticle outlet in freezer room did not have a cover.
Recent events (1)
  • · Z (O) $0

1910.305 G02 III

Other-than-serious 2 instances 1 exposed
Issued
Sep 7, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:\\\\r\\\\n\\\\r\\\\na) In the boat house welding shop, an extension cord had loose plug.\\\\r\\\\n\\\\r\\\\nb) In the boat House garage area, an extension cord plugged into electric forklift lacked adequate strain relief.    Note: These items were corrected at the time of the inspection.
Recent events (1)
  • · Z (O) $0

View U.S. Geological Survey - Columbiariverresearchlab's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 330974726.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.