Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BRUSH CONTRACTORS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BRUSH CONTRACTORS, INC. in 1121 SOUTH HOULK ROAD, DELAWARE, OH 43015 (NAICS 238210). OSHA activity number 330986183.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Brush Contractors, INC. — free Get an email when a new federal OSHA severe-injury report for Brush Contractors, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1121 SOUTH HOULK ROAD
City
DELAWARE
State
OH
ZIP
43015
Mailing
5000 TRANSAMERICAN DRIVE, COLUMBUS, OH 43228
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
20
Ownership type
A

3 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 21, 2011
Abate by
Nov 25, 2011
Penalty
Initial $2,550 · Current $2,550
29 CFR 1926.403(b)(2):     Installation and use. Listed, labeled, or certified equipment shall be installed and used inaccordance with instructions included in the listing, labeling, or certification.    a.    a.    At the front entry way where a main electrical panel was located, the employer covered the energized electrical panel  with cardboard which was not approved for this use thereby exposing employees to a contact/fire explosion
Recent events (1)
  • — Z (S) $2550

1926.405 A02 II I

Serious Gravity 5 1 instance 20 exposed
Issued
Nov 21, 2011
Abate by
Nov 25, 2011
Penalty
Initial $2,550 · Current $2,550
29 CFR 1926.405(a)(2)(ii)(I):     Flexible cords and cables shall be protected from damage. Sharp corners and projections shallbe avoided. Flexible cords and cables may pass through doorways or other pinch points, if protection is provided to avoid damage.    a.    On the 2nd floor mechanical room where the employer ran tenmporary wiring between two panel boxes, the energized electrical wiring was pinched between the metal covers thereby exposing employees to a contact hazard.
Recent events (1)
  • — Z (S) $2550

1926.405 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 21, 2011
Penalty
Initial $2,040 · Current $2,040
29 CFR 1926.405(b)(1):     Conductors entering boxes, cabinets, or fittings. Conductors entering boxes, cabinets, or fittingsshall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Unused openings in cabinets, boxes, andfittings shall also be effectively closed.    a.    In the front entry way where an electrical panel was located which supplied temporary power to lighting and portable tools, there was an unused opening in the topm of the energized electrical panel thereby exposing employees to a contact hazard.
Recent events (1)
  • — Z (S) $2040

View Brush Contractors, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 330986183.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.