Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: FAA NW MOUNTAIN REGION TELECOMMUNICATIONS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of FAA NW MOUNTAIN REGION TELECOMMUNICATIONS in 1601 LIND AVE SW SUITE 140, RENTON, WA 98057 (NAICS 926120). OSHA activity number 331067058.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch FAA NW Mountain Region Telecommunications for free Get an email when a new federal OSHA severe-injury report for FAA NW Mountain Region Telecommunications is published. One employer, no account, unsubscribe in one click.
Site address
1601 LIND AVE SW SUITE 140
City
RENTON
State
WA
ZIP
98057
Mailing
1601 LIND AVE SW SUITE 200, RENTON, WA 98057
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
926120
Employees
30
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.302 B02

Repeat Gravity 1 2 instances 30 exposed
Issued
Sep 30, 2011
Abate by
Nov 15, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.302(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling:      a)  Telecommunications, where electrical equipment not used as listed or labeled included:    1. Cubicle, where an APC surge protector relocatable power tap was used to supply power to the cup heater and the California Accessories relocatable power tap was used to supply power to the Sallon hot plate.     2. Cubicle, where an APC surge protector relocatable power tap was daisy chained with a relocatable power tap and used to supply power to computer equipment.    The Federal Aviation Administration North West Mountain Region was previously cited for a violation of this standard which was contained in OSHA inspection no. 309091635, citation no. 2, item no. 2, issued on May 15, 2007 with respect to a workplace at Renton, WA.
Recent events (1)
  • · Z (R) $0

1904.40 A

Other-than-serious 1 instance 30 exposed
Issued
Sep 30, 2011
Abate by
Oct 30, 2011
Penalty
Initial $0 · Current $0
29 CFR �1904.40(a): Copies of records kept under Part 1904 requested by an authorized government representative were not provided within four (4) business hours:    Facility, where the OSHA 300 Logs and OSHA 300-A Summary forms for calendar years 2008, 2009, and 2010 were not provided.
Recent events (1)
  • · Z (O) $0

1910.37 B02

Other-than-serious 2 instances 30 exposed
Issued
Sep 30, 2011
Abate by
Nov 15, 2011
Penalty
Initial $0 · Current $0
29CFR 1910.37(b)(2): Each exit must be clearly visible and marked by a sign reading "Exit:"    a) Exit signs were not posted on the designated exit doors located in:    1. The Telecommunications Lab    2. The PBX Office
Recent events (1)
  • · Z (O) $0

1910.37 B04

Other-than-serious 1 instance 30 exposed
Issued
Sep 30, 2011
Abate by
Oct 30, 2011
Penalty
Initial $0 · Current $0
29CFR 1910.37(b)(4): Where the direction of travel to the exit or exit discharge was not immediately apparent, signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge:       a)  PBX Office, where directional signs were not posted in the hallway located outside of the designated exit door.
Recent events (1)
  • · Z (O) $0

1910.305 B02 I

Other-than-serious 1 instance 30 exposed
Issued
Sep 30, 2011
Abate by
Oct 30, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, or faceplate:    a) Telecommunications Lab, where the receptacle outlet located behind the work bench was not equipped with a faceplate.
Recent events (1)
  • · Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 30 exposed
Issued
Sep 30, 2011
Abate by
Oct 30, 2011
Penalty
Initial $0 · Current $0
29CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:    a)  Cubicle, where a yellow extension cord was used to supply power to the Ativa shredder and a desk light in the adjoining cubicle.
Recent events (1)
  • · Z (O) $0

1910.159 C10

Other-than-serious 1 instance 30 exposed
Issued
Sep 30, 2011
Abate by
Oct 30, 2011
Penalty
Initial $0 · Current $0
29CFR 1910.159(c)(10): The employer did not assure the minimum vertical clearance between sprinklers and material below was be 18 inches (45.7 cm):      a)  Telecommunications Lab, where cardboard boxes located on the top shelf of the storage rack were stored beneath the sprinkler head.
Recent events (1)
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 331067058.