OSHA Inspection: BUREAU OF LAND MANAGEMENT, CARSON CITY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUREAU OF LAND MANAGEMENT, CARSON CITY in 5665 MORGAN MILL ROAD, CARSON CITY, NV 89701 (NAICS 926140). OSHA activity number 331073684.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bureau of Land Management, Carson City for free Get an email when a new federal OSHA severe-injury report for Bureau of Land Management, Carson City is published. One employer, no account, unsubscribe in one click.
Site address
5665 MORGAN MILL ROAD
City
CARSON CITY
State
NV
ZIP
89701
Mailing
5665 MORGAN MILL ROAD, CARSON CITY, NV 89701
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
926140
Employees
130
Ownership type
Federal government (D)

6 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 1 instance 30 exposed
Issued
Dec 5, 2011
Abate by
Dec 8, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2):  An exit access must be at least 28 inches (71.1 cm) wide at all points. Where there is only one exit access leading to an exit or exit discharge, the width of the exit and exit discharge must be at least equal to the width of the exit access.    (a)  In the UPS room, the exit/egress access was 22 inches and obstructed by a file cabinet.
Recent events (1)
  • · Z (S) $0

1910.37 B02

Serious Gravity 5 1 instance 30 exposed
Issued
Dec 5, 2011
Abate by
Dec 8, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):   Each exit must be clearly visible and marked by a sign reading "Exit."    (a)  In the computer room , the exit door was not marked "EXIT".
Recent events (1)
  • · Z (S) $0

1910.37 B05

Serious Gravity 1 1 instance 30 exposed
Issued
Dec 5, 2011
Abate by
Dec 8, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5):  Each doorway or passage along an exit access that could be mistaken for an exit must be marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet).    (a)  In the main conference room, the door that leads to the audio visual room was not marked "NOT AN EXIT"
Recent events (1)
  • · Z (S) $0

1910.253 B04 III

Serious Gravity 5 1 instance 10 exposed
Issued
Dec 5, 2011
Abate by
Dec 8, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii):   Oxygen cylinders in storage shall be separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.    (a)  In the engine bay, the acetylene and oxygen cylinders were stored together on a two-wheel cart.
Recent events (1)
  • · Z (S) $0

1910.303 F02

Serious Gravity 1 1 instance 10 exposed
Issued
Dec 5, 2011
Abate by
Dec 8, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):   Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.    (a)  In the computer room of USBLM, not all the circuit breakers of the power panel DP were labeled for their purpose.
Recent events (1)
  • · Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 3 exposed
Issued
Dec 5, 2011
Abate by
Dec 8, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5):   Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.    (a)  In the equipment operator's office, the orange extension cord was missing a ground pin.
Recent events (1)
  • · Z (S) $0

View Bureau of Land Management, Carson City's full OSHA safety record →