FORT IRWIN, CA ·
OSHA Inspection: CALIFORNIA ARMY NATIONAL GUARD - FORT IRWIN MATES
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CALIFORNIA ARMY NATIONAL GUARD - FORT IRWIN MATES in BOX 105103, BLD 7727, FORT IRWIN, CA 92310 (NAICS 928110). OSHA activity number 331079350.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CALIFORNIA ARMY NATIONAL GUARD - FORT IRWIN MATES
- Site address
- BOX 105103, BLD 7727
- City
- FORT IRWIN
- State
- CA
- ZIP
- 92310
- Mailing
- BOX 105103, BLD 7727, FORT IRWIN, CA 92310
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 68
- Ownership type
- Federal government (D)
Citations
9 citations on file for this inspection.
1910.303 B07 IV
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: Maintenance Bay, Building 7737, Near emergency light 18 - On or about October 18, 2011, A flexible pendant cord wrapped around the structure of the exhaust venting system was damaged showing the conductors inside and exposing employees to electrical hazards.
Recent events (1)
- · Z (S) $0
1910.303 G02 I
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): Warehouse, Building 7727 - On or about October 18, 2011, Conductors entering the electrical control box were not guarded against inadvertent contact by employees where the conduit containing the conductors ended approximately six inches from the electrical control box.
Recent events (1)
- · Z (S) $0
1910.304 B03 II C 3
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(C)(3): Each cord set, attachment cap, plug, and receptacle of cord sets, and any equipment connected by cord and plug, was not visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage: Maintenance Bay, Building 7737 - On or about October 18, 2011, A flexible cord set in use had a damaged receptacle plug.
Recent events (1)
- · Z (S) $0
1910.305 B01 I
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed: Warehouse, Building 7727 - On or about October 18, 2011, The opening where 480VAC conductors enter the electrical control box was not closed around the conductors.
Recent events (1)
- · Z (S) $0
1910.305 G01 III
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iii): Flexible cords used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of 29 CFR 1910.305 were not energized from an approved receptacle outlet: Maintenance Bay, Building 7737 - On or about October 18, 2011, The employer allowed employees to connect surge suppressors to flexible cords in order to provide 115VAC service to appliances in the work area.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV D
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: (a) Maintenance Bay, Building 7737, Near emergency light 18 - On or about October 18, 2011, A flexible pendant cord was wrapped around the structure of the exhaust venting system mounted on the wall. (b) Maintenance Bay, Building 7737, Near emergency light 19 - On or about October 18, 2011, A flexible pendant cord was wrapped around the structure of the exhaust venting system mounted on the wall. (c) Maintenance Bay, Building 7737 - On or about October 18, 2011, A parts washer flexible cord was wrapped around the structure of the building. (d) Warehouse, Building 7727 - On or about October 18, 2011, A flexible cord was run through a metal sleeve attached to the building wall.
Recent events (1)
- · Z (S) $0
1904.29 B01
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.29(b)(1): A Log of all recordable work-related injuries and illnesses (OSHA Form 300 or equivalent), was not completed in the detail as required by the regulation. (a) At the establishment - On or about October 18, 2011, the employer failed to complete the OSHA Form 300 Log of recordable work-related injuries and illnesses - column (F) describing the object/substance that directly injured or made person ill for the years 2007, 2008, 2009, 2010 and 2011.
Recent events (1)
- · Z (O) $0
1904.29 B01
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.29(b)(1): A Log of all recordable work-related injuries and illnesses (OSHA Form 300 or equivalent), was not completed in the detail as required by the regulation. (a) At the establishment - On or about October 18, 2011, the employer failed to complete the 2010 OSHA Form 300 Log of recordable work-related injuries and illnesses in that the ten names of the employees (B) were not completely indicated. (b) At the establishment - On or about October 18, 2011, the employer failed to complete the 2010 OSHA Form 300 Log of recordable work-related injuries and illnesses in that the ten cases were not classified by checking the box indicating the most serious outcome of each case (G, H, I, or J). (c) At the establishment - On or about October 18, 2011, the employer failed to complete the 2010 OSHA Form 300 Log of recordable work-related injuries and illnesses in that the "injury" column (M) was misreported for case number 9.
Recent events (1)
- · Z (O) $0
1904.32 A01
- Issued
- Jan 20, 2012
- Abate by
- Feb 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.32(a)(1): A review of the OSHA Log of Recordable Work-Related Injuries and Illnesses (OSHA Form 300 or equivalent) was not completed to ensure the Log was accurate and complete, and/or deficiencies were not identified and corrected at the end of each calendar year: (a) At the establishment - On or about October 18, 2011, On the 2010 OSHA Form 300A, the employer listed erroneous data for entries "Total number of cases with days away from work" (H) (b) At the establishment - On or about October 18, 2011, On the 2010 OSHA Form 300A, the employer listed erroneous data for entries "Total number of cases with job transfer or restriction" (I) (c) At the establishment - On or about October 18, 2011, On the 2010 OSHA Form 300A, the employer listed erroneous data for entries "Total number of.. (M): (1) Injury, (2) Skin Disorder, and (3) Respiratory Condition.
Recent events (1)
- · Z (O) $0
More inspections in this industry (NAICS 928110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 331079350.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.