OSHA Inspection: BIG LOTS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BIG LOTS, INC. in 500 PHILLIPI ROAD, COLUMBUS, OH 43228 (NAICS 493110). OSHA activity number 331084392.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch BIG Lots, INC. for free Get an email when a new federal OSHA severe-injury report for BIG Lots, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
BIG LOTS, INC.
Site address
500 PHILLIPI ROAD
City
COLUMBUS
State
OH
ZIP
43228
Mailing
300 PHILLIPI ROAD, COLUMBUS, OH 43228
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
550
Ownership type
Private (A)

6 citations on file for this inspection.

1910.212 A03 II

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 10, 2011
Abate by
Dec 10, 2011
Penalty
Initial $4,400 · Current $2,640 Reduced
29 CFR 1910.212(a)(3)(ii):  The point of operation of machines whose operation exposes an employee to injury, shall beguarded. The guarding device shall be in conformity with any appropriate standards therefor, or, in the absence of applicable specific standards,shall be so designed and constructed as to prevent the operator from having any part of his body in the danger zone during the operatingcycle:    a.  In building 450 in the forklift maintenance shop, the point of operation on the150 ton hydraulic tire press (model: 150) was not guarded.
Recent events (2)
  • · I (S) $2640
  • · Z (S) $4400

1910.305 B01 II

Serious Gravity 1 2 instances 1 exposed
Issued
Nov 10, 2011
Abate by
Nov 17, 2011
Penalty
Initial $3,300 · Current $1,980 Reduced
29 CFR 1910.305(b)(1)(ii):  Unused openings in cabinets, boxes, and fittings shall be effectively closed:    a.  In the 200 battery changing area, the metal wireway which powers the chargers did not have a cover on the open end.    b.  In the 400 receiving dock, the access door for the burner panel was damaged and partially open on the HU-4C heating unit.
Recent events (2)
  • · I (S) $1980
  • · Z (S) $3300

1910.332 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 10, 2011
Abate by
Dec 10, 2011
Penalty
Initial $5,500 · Current $3,300 Reduced
29 CFR 1910.332(b)(1):  Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments:    a.  At the workplace, employees who performed work on or near energized parts up to 480 VAC such as testing, troubleshooting, voltage measuring, and other tasks had not received training on the specific hazards associated with electrical energy and safety-related work practices and requirements as necessary to provide protection from electrical hazards such as contact and arc flash.
Recent events (2)
  • · I (S) $3300
  • · Z (S) $5500

1910.335 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 10, 2011
Abate by
Dec 10, 2011
Penalty
Initial $0 · Current $0
29 CFR 1910.335(b)(1):  Safety signs and tags.  Safety signs, safety symbols, or accident prevention tags shall be usedwhere necessary to warn employees about electrical hazards which may endanger them, as required by 1910.145:    a.  At the workplace, control panels, service panels, distribution panels, transformers, and/or other electrical cabinets including, but not limited to, the main control panel CP-10 for sortation, control panel CP-4 for module 4, control panel CP-3 for module 3, and control panel CP-17 for the extendable truck loader were not marked to warn employees of the potential electric arc flash hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.333 A02

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 10, 2011
Abate by
Mar 16, 2012
Penalty
Initial $5,500 · Current $3,300 Reduced
29 CFR 1910.333(a)(2):  "Energized parts." If the exposed live parts are not deenergized (i.e., for reasons of increased oradditional hazards or infeasibility), other safety-related work practices shall be used to protect employees who may be exposed to the electricalhazards involved. Such work practices shall protect employees against contact with energized circuit parts directly with any part of their body orindirectly through some other conductive object. The work practices that are used shall be suitable for the conditions under which the work is to beperformed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph(c) of this section:    a.  At the workplace for employees who routinely performed work on or near energized parts up to 480 VAC such as testing, troubleshooting, voltage measuring, and other tasks, neither a flash hazard analysis was conducted to determine the proper protection nor a flash protection boundary established to protect employees from arc flash hazards.    ABATEMENT NOTE:  One method of abatement among others, includes conducting a Flash Hazard Analysis in compliance with NFPA 70E Standard for Electrical Safety in the Workplace (2009 Edition), Article 130.3 (or its equivalent), to determine the Flash Hazard Boundary and the use of electrical protective equipment necessary for the specific related hazards of each task.
Recent events (2)
  • · I (S) $3300
  • · Z (S) $5500

1910.335 A01 I

Repeat Gravity 5 1 instance 1 exposed
Issued
Nov 10, 2011
Abate by
Dec 10, 2011
Penalty
Initial $27,500 · Current $16,500 Reduced
29 CFR 1910.335(a)(1)(i):  Employees working in areas where there are potential electrical hazards shall be provided with,and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to beperformed.  Note: Personal protective equipment requirements are contained in subpart I of this part:    a.  At the workplace for employees who routinely performed work on or near energized parts up to 480 VAC such as testing, troubleshooting, voltage measuring, and other tasks, the employer did not enforce the use of electrical protective equipment which was necessary for the electrical hazards of arc flash or shock.    Big Lots, Inc., was previously cited for a violation of this occupational safety and health standard 29CFR 1910.335(a)(1)(i), which was contained in OSHA inspection number 312497282, citation number 1, item number 3 and was affirmed as a final order on May 27, 2009, with respect to a workplace located at 2855 Selma Highway, Montgomery, AL 36108.
Recent events (2)
  • · I (R) $16500
  • · Z (R) $27500