Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,871Inspections Most recent open 2026-07-30 Last loaded 2026-08-03

OSHA Inspection: TRIPLE D ENTERPRISES

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of TRIPLE D ENTERPRISES in 9732 S. MERTON AVENUE, OAK LAWN, IL 60453 (NAICS 236118). OSHA activity number 331084590.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Triple D Enterprises for free Get an email when a new federal OSHA severe-injury report for Triple D Enterprises is published. One employer, no account, unsubscribe in one click.
Site address
9732 S. MERTON AVENUE
City
OAK LAWN
State
IL
ZIP
60453
Mailing
3400 W 111TH STREET PMB 116, CHICAGO, IL 60655
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236118
Employees
5
Ownership type
A

5 citations on file for this inspection.

1926.403 I02 I

Serious Gravity 1 1 instance 1 exposed
Issued
Dec 9, 2011
Abate by
Dec 14, 2011
Penalty
Initial $1,800 · Current $720 Reduced
29 CFR 1926.403(I)(2)(i):  Except as required or permitted else where in this subpart, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by cabinets or other forms of enclosures, or by any of the following means:    On or about August 16, 2011, at the jobsite located at 9732 S. Merton Avenue, Oak Lawn, Illinois - employees were working in a rehab using receptacles and light swtiches that were not protected with covers or face plates to protect against accidental contact, thereby exposing employees to electrical hazards.
Recent events (2)
  • · I (S) $720
  • · Z (S) $1800

1926.404 B01 I

Serious Gravity 1 1 instance 1 exposed
Issued
Dec 9, 2011
Abate by
Dec 14, 2011
Penalty
Initial $0 · Current $0
29 CFR 1926.404(b)(1)(i):  The employer shall use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors.    On or about August 16, 2011, at the jobsite located at 9732 S. Merton Avenue, Oak Lawn, Illinois - employees were using electric tools such as, but not limited to, power drills and radios were not using ground faults circuit interrupters or did not have an assured equipment grounding program, thereby exposing employees to electrical hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.405 A02 II E

Serious Gravity 1 4 instances 1 exposed
Issued
Dec 9, 2011
Abate by
Dec 14, 2011
Penalty
Initial $1,800 · Current $720 Reduced
29 CFR 1926.405(a)(2)(ii)(E): All lamps for general illumination shall be protected from accidental contact or breakage. Metal-case sockets shall be grounded:    On or about August 16, 2011, at the jobsite located at 9732 S. Merton Avenue, Oak Lawn, Illinois - employees performing drywall work in a rehab were exposed to electrical hazards due to the lights having missing cages.
Recent events (2)
  • · I (S) $720
  • · Z (S) $1800

1926.405 A02 II F

Serious Gravity 1 2 instances 1 exposed
Issued
Dec 9, 2011
Abate by
Dec 14, 2011
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(F):  Temporary lights shall not be suspended by their electric cords unless cords and lights are designed for this means of suspension:    On or about August 16, 2011, at the jobsite located at 9732 S. Merton Avenue, Oak Lawn, Illinois - employees were performing drywall activities in a rehab where the lights were suspended by their cord, thereby exposing employees to electrical hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.405 B02

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 9, 2011
Abate by
Dec 14, 2011
Penalty
Initial $0 · Current $0
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings shall be provided with covers. If metal covers are used, they shall be grounded. In energized installations each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:    On or about August 16, 2011, at the jobsite located at 9732 S. Merton Avenue, Oak Lawn, Illinois - employees were performing drywall activities in a rehab where the electrical panel box was not equipped with a cover, thereby exposing employees to electrical hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331084590.