SANTA ROSA, CA ·
OSHA Inspection: CALIFORNIA ARMY NATIONAL GUARD FMS #34
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CALIFORNIA ARMY NATIONAL GUARD FMS #34 in 1500 ARMORY DRIVE, SANTA ROSA, CA 95401 (NAICS 928110). OSHA activity number 331086397.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CALIFORNIA ARMY NATIONAL GUARD FMS #34
- Site address
- 1500 ARMORY DRIVE
- City
- SANTA ROSA
- State
- CA
- ZIP
- 95401
- Mailing
- 1500 ARMORY DRIVE, SANTA ROSA, CA 95401
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 9
- Ownership type
- Federal government (D)
Citations
5 citations on file for this inspection.
1910.305 A02 X
- Issued
- Dec 2, 2011
- Abate by
- Dec 23, 2011
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables shall be protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points. a) East Bay 2 : On August 1, 2011, and at times prior thereto, a flexible cord was laying across the aisle unprotected near the POL storage #6 & #7 and the Special Tool holding area creating a hazard.
Recent events (1)
- · Z (S) $0
1910.157 B01
- Issued
- Dec 2, 2011
- Abate by
- Dec 23, 2011
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(b)(1): Where the employer has established and implemented a written fire safety policy which requires the immediate and total evacuation of employees from the workplace upon the sounding of a fire alarm signal and which includes an emergency action plan and a fire prevention plan which meet the requirements of 29 CFR 1910.38 and 29 CFR 1910.39 respectively, and when extinguishers are not available in the workplace, the employer is exempt from all requirements of this section unless a specific standard in part 1910 requires that a portable fire extinguisher be provided. a) Bays 1-4: On or about August 1, 2011, and at times prior thereto, the Emergency Fire Evacuation Maps posted did not show current changes in the evacuation routes and assembly areas for meeting points 1 & 2.
Recent events (1)
- · Z (S) $0
1910.305 B01 II
- Issued
- Dec 2, 2011
- Abate by
- Dec 23, 2011
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. a) West: Mezzanine Level - Lunch Room: On or about August 1, 2011, and at times prior thereto, there was a 4 square unmounted metal box with a loosened knock out on the underside located on top of a wooden cabinet.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV A
- Issued
- Dec 2, 2011
- Abate by
- Dec 23, 2011
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): As a substitute for the fixed wiring of a structure; East-Bay 2 : On August 1, 2011, and at times prior thereto, a flexible cord was used in place of fixed wiring from the outlet above the flammable storage cabinet # 6 running across the floor through a hole in the rear of the desk.
Recent events (1)
- · Z (S) $0
1910.303 E01
- Issued
- Dec 2, 2011
- Abate by
- Dec 23, 2011
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e)(1): Identification of manufacturer and ratings. Electric equipment did not have markings giving voltage, current, wattage, or other ratings as necessary showing manufacturer's name or trademark. Bay 2: On August 1, 2011, and at times prior thereto, a flexible cord was used in place of fixed wiring from the outlet above the flammable storage cabinet # 6 running across the floor through a hole in the rear of the desk. The flexible cord was plugged into a 4 square unmounted metal box placed on a metal trash can with plastic liner under the desktop creating an electrical and fire hazard .
Recent events (1)