BURKETTSVILLE, OH ·
OSHA Inspection: WERLING AND SONS, INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of WERLING AND SONS, INC. in 100 S. PLUM ST., BURKETTSVILLE, OH 45310 (NAICS 311612). OSHA activity number 331089748.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WERLING AND SONS, INC.
- Site address
- 100 S. PLUM ST.
- City
- BURKETTSVILLE
- State
- OH
- ZIP
- 45310
- Mailing
- 100 S. PLUM ST., BURKETTSVILLE, OH 45310
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311612
- Employees
- 19
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.147 C04 I
- Issued
- Jan 27, 2012
- Abate by
- Jan 30, 2012
- Penalty
- Initial $3,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) On or about November 14, 2011, the employer had not established Energy Control Procedures for the employees who performed servicing and maintenance on equipment with in the facility. The employer did not have procedures to isolate and lockout the energy sources to boiler equipment such as the hot water supply line(s) and the electric disconnect.
Recent events (2)
- · I (S) $1500
- · Z (S) $3000
1910.303 F02
- Issued
- Jan 27, 2012
- Abate by
- Jan 31, 2012
- Penalty
- Initial $1,800 · Current $400 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) On or about November 14, 2011, the 200-Amp feeder electric breaker panel located outside the Boiler Room and the wall-mounted branch circuit breaker panel located inside the boiler room did not have the over current breaker devices in each panel labeled to identify to its service location.
Recent events (2)
- · I (O) $400
- · Z (S) $1800
1910.332 B01
- Issued
- Jan 27, 2012
- Abate by
- Jan 30, 2012
- Penalty
- Initial $4,200 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) On or about the November 14, 2011, an employee was working on electrical equipment at the facility that was an energized 208 AC volt 3 Phase circuit located in the boiler room without properly isolating the power fromo the equipment. The employee was exposed to electrical hazards but was not instructed in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to assist in the control or elimination of any hazards or other exposure to illness or injury. The employee was not trained in and familiar with the potential hazards to which he was exposed nor any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 1910.335 but which were necessary for the employee's safety.
Recent events (2)
- · I (S) $2100
- · Z (S) $4200
1910.333 A01
- Issued
- Jan 27, 2012
- Abate by
- Jan 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee could be exposed to were not deenergized before the employee worked on or near them: a) On or about November 14, 2011 the employer did not ensure that the live 208 AC volt 3 Phase elctric branch circuit service to the Boiler number 2 circulation pump was first de-energized prior to the employee making repairs to the electric equipment.
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections at Werling and Sons, INC.