Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NEW METHOD LAUNDRY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NEW METHOD LAUNDRY in 315 MAIN STREET, CANON CITY, CO 81212 (NAICS 812320). OSHA activity number 331096008.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NEW Method Laundry — free Get an email when a new federal OSHA severe-injury report for NEW Method Laundry is published. One employer, no account, unsubscribe in one click.
Establishment
NEW METHOD LAUNDRY
Site address
315 MAIN STREET
City
CANON CITY
State
CO
ZIP
81212
Mailing
315 MAIN STREET, CANON CITY, CO 81212
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
812320
Employees
12
Ownership type
A

6 citations on file for this inspection.

1910.151 C

Serious Gravity 5 2 exposed
Issued
Dec 9, 2011
Abate by
Jan 3, 2012
Penalty
Initial $2,040 · Current $1,100 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:    1) On November 29, 2011, and at prior times, an eye wash facility was not provided where employees work with corrosive chemicals used in the commercial laundry washers.
Recent events (2)
  • — I (S) $1100
  • — Z (S) $2040

1910.305 A01 I

Serious Gravity 5 2 exposed
Issued
Dec 9, 2011
Abate by
Jan 3, 2012
Penalty
Initial $2,040 · Current $1,100 Reduced
29 CFR 1910.305(a)(1)(i):  Metal raceways, cable armor, and other metal enclosures for conductors were not connected to all boxes, fittings, and cabinets to provide effective electrical continuity:    1) On November 29, 2011, and at prior times, the metal electrical conduit was not attached to the knife switch for the heater.
Recent events (2)
  • — I (S) $1100
  • — Z (S) $2040

1910.305 B01

Serious Gravity 5 2 exposed
Issued
Dec 9, 2011
Abate by
Jan 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1): Unused openings in boxes, cabinets, or fittings were not effectively closed:    1) On November 29, 2011, and at prior times, knockouts were not closed on the knife switch box for the heater.    2) On November 29 2011, and at prior times, blanks were not installed to cover unused openings in the breaker panel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02

Serious Gravity 5 2 exposed
Issued
Dec 9, 2011
Abate by
Jan 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2):  Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:    1) On November 29, 2011, and at prior times, covers were missing on junction boxes for the 220 volt line leading to the compressor.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 2 exposed
Issued
Dec 9, 2011
Abate by
Jan 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i):  Live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures:    1) On November 29, 2011, the door on the breaker panel was left in an open position.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01

Other-than-serious 2 exposed
Issued
Dec 9, 2011
Abate by
Jan 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:  Employees work with hazardous chemicals such as perchloroethylene and caustic cleaners.  The employer had not developed a written hazard communication program.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View NEW Method Laundry's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331096008.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.