OSHA Inspection: DAVE SMITH CHEVROLET OLDSMOBILE PONTIAC CADILLAC, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of DAVE SMITH CHEVROLET OLDSMOBILE PONTIAC CADILLAC, INC. in 210 N. DIVISION, KELLOGG, ID 83837 (NAICS 441110). OSHA activity number 331098194.

Watch Dave Smith Chevrolet Oldsmobile Pontiac Cadillac, INC. — free Get an email when a new federal OSHA severe-injury report for Dave Smith Chevrolet Oldsmobile Pontiac Cadillac, INC. is published. One employer, no account, unsubscribe in one click.
Site address
210 N. DIVISION
City
KELLOGG
State
ID
ZIP
83837
Mailing
210 N. DIVISION, KELLOGG, ID 83837
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441110
Employees
60
Ownership type
A

5 citations on file for this inspection.

1926.403 I01 I

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $4250.00 · Current $2600.00 Reduced
29 CFR 1926.403(i)(1)(i):  Workspace, in front of electric equipment operating at 600 volts, nominal, or less, was less than 30 inches wide:      (a)  Mezzanine level electrical panel box, on or about November 29, 2011, and at times prior thereto, maintenance employees working approximately within a 20 inch space while isolating wires to demolish and exposed to 120V single phase energized conductors on each leg of the open electrical panel.    Note: Abatement certification IS required for this item.
Recent events (2)
  • — I (S) $2600
  • — Z (S) $4250

1926.405 D

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00

Hazardous substances 8870

29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front:      (a)  Mezzanine level electrical panel box, on or about November 29, 2011, and at times prior thereto, maintenance employees working with electrical being demolished, were exposed to 120V single phase energized conductors on each leg of the open electrical panel while attempting to isolate wiring for demolition.        Note: Abatement certification IS required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.416 A01

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00

Hazardous substances 8870

29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:      (a)  Mezzanine level electrical panel box, on or about November 29, 2011, and at times prior thereto, maintenance employees working with electrical being demolished, were exposed to 120V single phase energized conductors on each leg of the open electrical panel while attempting to isolate wiring for demolition.        Note: Abatement certification IS required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B04

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(4):  Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:      (a)  On or about November 29, 2011, and at times prior thereto, at the mezzanine level, office employees were exposed fire evacuation hazards.         Note: Abatement certification IS required for this item.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B02 I

Other-than-serious 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00

Hazardous substances 8870

29 CFR 1910.305(b)(2)(i):  Pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose:      (a)  Mezzanine level, on or about November 29, 2011, and at times prior thereto, electrical junction box along the walkway to the computer room where office employees were exposed to 120V single phase energized conductors of an uncovered junction box.       Note: Abatement certification IS required for this item.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0