Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: SANCHO CONSTRUCTORS LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SANCHO CONSTRUCTORS LLC in 1325 19TH AVE W, WILLISTON, ND 58801 (NAICS 238130). OSHA activity number 331101402.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sancho Constructors LLC for free Get an email when a new federal OSHA severe-injury report for Sancho Constructors LLC is published. One employer, no account, unsubscribe in one click.
Site address
1325 19TH AVE W
City
WILLISTON
State
ND
ZIP
58801
Mailing
P.O. BOX 69, COLUMBIA FALLS, MT 59912
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238130
Employees
7
Ownership type
Private (A)

3 citations on file for this inspection.

1926.403 I01 II

Serious Gravity 10 6 instances 20 exposed
Issued
Apr 26, 2012
Abate by
Apr 27, 2012
Penalty
Initial $4,200 · Current $4,200
29 CFR 1926.403(i)(1)(ii):  Working space about electric equipment operating at 600 volts, nominal, or less was used for storage:      a)  On or about November 2, 2011 and at times prior Sancho Constructors LLC as the controlling contractor did not ensure that workers were protected from electrical hazards.  Several crews stored materials and trash in the electrical rooms.
Recent events (1)
  • · Z (S) $4200

1926.403 I02 I

Serious Gravity 10 6 instances 20 exposed
Issued
Apr 26, 2012
Abate by
Apr 27, 2012
Penalty
Initial $0 · Current $0
29 CFR 1926.403(i)(2)(i):  Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.      a)  On or about November 2, 2011 and at times prior, Sancho Constructors LLC as the controlling contractor did not ensure that workers were protected from electrical hazards.  Crews of nonelectrical workers did work in the electrical rooms where the panels were live and had inadequate or no covers.
Recent events (1)
  • · Z (S) $0

1926.405 B01

Serious Gravity 10 6 instances 20 exposed
Issued
Apr 26, 2012
Abate by
Apr 27, 2012
Penalty
Initial $0 · Current $0
29 CFR 1926.405(b)(1):  Conductors entering boxes, cabinets, and fittings were not protected from abrasion:      a)  On or about November 2, 2011 and at times prior, Sancho Constructors LLC as the controlling contractor did not ensure that workers were protected from electrical hazards.  Crews of nonelectrical workers were working in the electrical rooms where improper connections had been made.  The conductors feeding the temporary panels were not protected from abrasion, as they were strung over the edge of the panel boxes.
Recent events (1)
  • · Z (S) $0

View Sancho Constructors LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 331101402.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.