Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ELECTRICAL SYSTEMS INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of ELECTRICAL SYSTEMS INC. in 1325 19TH AVE. W, WILLISTON, ND 58801 (NAICS 238210). OSHA activity number 331101907.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Electrical Systems INC. — free Get an email when a new federal OSHA severe-injury report for Electrical Systems INC. is published. One employer, no account, unsubscribe in one click.
Site address
1325 19TH AVE. W
City
WILLISTON
State
ND
ZIP
58801
Mailing
20 CONESTOGA CT., KALISPELL, MT 59901
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

3 citations on file for this inspection.

1926.403 I01 II

Serious Gravity 10 6 instances 20 exposed
Issued
Apr 26, 2012
Abate by
Apr 27, 2012
Penalty
Initial $4,200 · Current $2,100 Reduced
29 CFR 1926.403(i)(1)(ii):  Working space about electric equipment operating at 600 volts, nominal, or less was used for storage:      a)  On or about November 2, 2011 and at times prior Electrical Systems Inc. as the creating contractor did not ensure that employees/workers were protected from electrical hazards.  The electricians stored materials and allowed other crews materials to be stored in the electrical room.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $4200

1926.403 I02 I

Serious Gravity 10 6 instances 20 exposed
Issued
Apr 26, 2012
Abate by
Apr 27, 2012
Penalty
Initial $0 · Current $0
29 CFR 1926.403(i)(2)(i):  Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.      a)  On or about November 2, 2011 and at times prior, Electrical Systems Inc. as the creating/exposing contractor did not ensure that employees/workers were protected from electrical hazards.  Crews of subcontractors and electricians did work in the electrical rooms where the panels were live and had inadequate or no covers.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B01

Serious Gravity 10 6 instances 20 exposed
Issued
Apr 26, 2012
Abate by
Apr 27, 2012
Penalty
Initial $0 · Current $0
29 CFR 1926.405(b)(1):  Conductors entering boxes, cabinets, and fittings were not protected from abrasion:      a)  On or about November 2, 2011 and at times prior, Electrical Systems Inc. as the creating/exposing contractor did not ensure that employees/workers were protected from electrical hazards.  Crews of different skills including the electricians who did the work were exposed to improper conductor installation.  The conductors feeding the temporary panels were not protected from abrasion, as they were strung over the edge of the panel boxes.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Electrical Systems INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331101907.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.