Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: COLBY METAL INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of COLBY METAL INC. in 701 INDUSTRIAL DR., COLBY, WI 54421 (NAICS 332999). OSHA activity number 331106740.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Colby Metal INC. — free Get an email when a new federal OSHA severe-injury report for Colby Metal INC. is published. One employer, no account, unsubscribe in one click.
Establishment
COLBY METAL INC.
Site address
701 INDUSTRIAL DR.
City
COLBY
State
WI
ZIP
54421
Mailing
PO BOX 466, COLBY, WI 54421
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332999
Employees
61
Ownership type
A

8 citations on file for this inspection.

1910.107 B05 IV

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 11, 2012
Abate by
Oct 18, 2012
Penalty
Initial $2,142 · Current $1,500 Reduced
29 CFR 1910.107(b)(5)(iv):     Spaces within the spray booth on the downstream and upstream sides of filters were not protected with approved automatic sprinklers:      a.) On or about 12/28/2011, the dry filter type spray booth for electrostatic paint application was not equipped with automatic sprinklers or an alternate system for fire protection on either the upstream or the downstream areas.                     Abatement Certification and  Documentation required.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2142

1910.107 B09

Serious Gravity 1 1 instance 10 exposed
Issued
Jun 11, 2012
Abate by
Jun 12, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.107(b)(9):     A clear space of not less than 3 feet on all sides was not kept free from storage or combustible construction:      a.) On or about 12/28/2011, cardboard boxes were stored adjacent to the powder spray booth.                               Abatement Certification and  Documentation required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.107 C04

Serious Gravity 1 1 instance 10 exposed
Issued
Jun 11, 2012
Abate by
Sep 5, 2012
Penalty
Initial $1,607 · Current $1,120 Reduced
29 CFR 1910.107(c)(4):     Electrical wiring and equipment did not conform to the provisions of 29 CFR 1910.107(c) and was not otherwise  in accordance with 29 CFR Subpart S, in that Class II, Division 1 or 2 approved equipment and wiring was not used where deposits of combustible residues could readily accumulate:     a.) On or about 12/28/2011,  powder residue was noted on the floor outside the booth and  accumulated on a plug-in connection for equipment in the powder spray booth.   This plug-in and other electrical connections immediately outside the booth were not approved for Class II, Division 1 or 2 locations.                           Abatement Certification and  Documentation required.
Recent events (2)
  • — I (S) $1120
  • — Z (S) $1606.5

1910.107 L04 I

Serious Gravity 1 1 instance 10 exposed
Issued
Jun 11, 2012
Abate by
Jul 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.107(l)(4)(i):     All areas were not kept free of the accumulation of powder coating dust:    a.)  On or about 12/28/2011, there was spray powder residue located on the floor outside the spray booth.                      Abatement Certification and  Documentation required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.307 C02 I

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 11, 2012
Abate by
Sep 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.307(c)(2)(i):     Equipment was not approved for the class of location and for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that would be present:      a.) On or about 12/28/2011, spray powder residue was noted on the floor outside the booth and  accumulated on a plug-in connection for equipment in the powder spray booth.   The spray powder is identified by the manufacturer as having the potential for explosive condition.  The plug-in and other electrical connections immediately outside the booth were not approved for Class II, Division 1 or 2 locations.                           Abatement Certification and  Documentation required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.107 L07 V

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 11, 2012
Abate by
Jul 24, 2012
Penalty
Initial $3,213 · Current $2,250 Reduced
29 CFR 1910.107(l)(7)(v):     The electrical equipment was not interlocked with the ventilation system so that the equipment could not be operated unless the ventilation fans were in operation:      a.)  On or about 12/28/2011, the powder spray booth was operated without an interlock to ensure that application could only occur while the ventilation was operational.                                      Abatement Certification and  Documentation required.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $3213

1910.1200 F05 I

Other-than-serious 1 instance 3 exposed
Issued
Jun 11, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(5)(i):     The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein:    a.)  On or about 12/28/2011, a spray bottle of Simple Green All-Purpose Cleaner which contains 2-Butoxyethanol had a label that was illegible, such that the identifying name was unclear.                       Abatement Certification or Documentation not required.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 F05 I

Other-than-serious 1 instance 3 exposed
Issued
Jun 11, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(5)(i):     The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein:    a.)  On or about 12/28/2011, a spray bottle of Simple Green All-Purpose Cleaner which contains 2-Butoxyethanol had a label that was illegible, such that the hazard warning advising possible skin or respiratory irritation was unclear.                            Abatement Certification or Documentation not required.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Colby Metal INC.'s full OSHA safety record →