OSHA Inspection: LAKE ERIE ELECTRIC OF TOLEDO INC.

Unprogrammed Related inspection · Health discipline

On , OSHA opened an unprogrammed Related health inspection of LAKE ERIE ELECTRIC OF TOLEDO INC. in 1155 BIBLE RD, LIMA, OH 45801 (NAICS 238210). OSHA activity number 331110833.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Lake Erie Electric of Toledo INC. for free Get an email when a new federal OSHA severe-injury report for Lake Erie Electric of Toledo INC. is published. One employer, no account, unsubscribe in one click.
Site address
1155 BIBLE RD
City
LIMA
State
OH
ZIP
45801
Mailing
25730 1ST STREET, WESTLAKE, OH 44145
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
120
Ownership type
A

1 citation on file for this inspection.

1926.416 A03

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 4, 2012
Penalty
Initial $5,670 · Current $3,969 Reduced
29 CFR 1926.416(a)(3):     Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into pysical or electrical contact with the electric power circuit.    a)  Lake Erie Electric of Toledo, Inc., working at the Ford Engine Plant at 1155 Bible Road in Lima, Oh: On or about December 22, 2011, the employer did not assure that the work being performed by subcontractor employees prevented exposure to energized electrical conductors; in that the employer did not properly mark conductors in the cable tray which were to be removed.  A subcontractor employee was exposed to an arch flash/blast when cutting into an energized 480 volt conductor.
Recent events (3)
  • · F (S) $3969
  • · C (S) $5670
  • · Z (S) $5670

View Lake Erie Electric of Toledo INC.'s full OSHA safety record →