Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: MARAMONT CORP

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MARAMONT CORP in 5600 1ST AVENUE BLDG C, BROOKLYN, NY 11220 (NAICS 493120). OSHA activity number 331902528.

Watch Maramont Corp — free Get an email when a new federal OSHA severe-injury report for Maramont Corp is published. One employer, no account, unsubscribe in one click.
Establishment
MARAMONT CORP
Site address
5600 1ST AVENUE BLDG C
City
BROOKLYN
State
NY
ZIP
11220
Mailing
5600 1ST AVENUE BLDG C, BROOKLYN, NY 11220
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
73
Ownership type
A

7 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 1 instance 31 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $2400.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    Located at 5600 1st Avenue, Building C, Brooklyn, NY    On or about 1/24/2012    An electric panelboard was not legibly marked to indicate the purpose of each panelboard breaker in the panelboard.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $3500

1910.305 B01 II

Serious Gravity 5 1 instance 31 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii):  Unused openings in boxes, cabinets, or fittings were not effectively closed:    Located at 5600 1st Avenue, Building C, Brooklyn, NY    On or about 1/24/2012    An electric panelboard with missing cabinet parts ws not effectively closed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 1 instance 17 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $2400.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective    Located at 5600 1st Avenue, Building C, Brooklyn, NY    On or about 1/24/2012    A triangle portable cooler (fan) model #PC4213 SN#B06 was being used in loading dock area and the power cord was cut and spliced and was missing a ground pin.  Portable cooler(fan) used to dry water on floor.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $3500

1910.305 G02 II

Serious Gravity 5 1 instance 17 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(ii):  Flexible cords were not used only in continuous lengths without splice or tap:    Located at 5600 1st Avenue, Building C, Brooklyn, NY    On or about 1/24/2012    A triangle portable cooler (fan) model #PC4213 SN#B06 was being used in loading dock area and the cord was cut and spliced and was missing a ground pin.  Portable cooler(fan) used to dry water on floor.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 D01

Serious Gravity 5 2 instances 31 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1910.36(d)(1):  Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:    Located at 5600 1st Avenue, Building C, Brooklyn, NY    On or about 1/24/2012    1)An emergency exit door in baby food room was marked with mixed signage "No Exit" and "Emergency Exit Only" and the emergency door was locked with a bolt latch.    2)An emergency exit located in back of line 7 had screen door in font of emergency exit.
Recent events (2)
  • — I (S) $2800
  • — Z (S) $2800

1910.37 B04

Serious Gravity 5 1 instance 31 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $0.00 Reduced
29 CFR 1910.37(b)(4):  Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:    Located at 5600 1st Avenue, Building C, Brooklyn, NY    On or about 1/24/2012    The employer did not ensure that directional signs were posted throughout the facility to indicate the locations of the nearest emergency exits in the event of an emergency.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2800

1910.37 B05

Serious Gravity 5 1 instance 31 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(5):  Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):    Located at 5600 1st Avenue, Building C, Brooklyn, NY    On or about 1/24/2012    The employer did not ensure that doorways in the warehouse that could be mistaken for an exit was labeled as not an exit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331902528.