CLEVELAND, OH —
OSHA Inspection: ARTISAN INDUSTRIES INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ARTISAN INDUSTRIES INC. in 4911 GRANT AVENUE, CLEVELAND, OH 44125 (NAICS 332999). OSHA activity number 331903260.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARTISAN INDUSTRIES INC.
- Site address
- 4911 GRANT AVENUE
- City
- CLEVELAND
- State
- OH
- ZIP
- 44125
- Mailing
- 1760 MILLER PARKWAY, STREETSBORO, OH 44241
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332999
- Employees
- 18
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.179 J02
- Issued
- Apr 10, 2012
- Abate by
- May 1, 2012
- Penalty
- Initial $2,100 · Current $1,365 Reduced
General-duty citation text
29 CFR 1910.179(j)(2): The items listed in subparagraphs (j)(2)(i)-(vii) were not inspected for defects at intervals as defined in paragraph (j)(1)(ii) of this section or as specifically indicated, and all deficiencies were not carefully examined and a determination made as to whether they constituted a safety hazard: On and before 1/30/2012, the Beacon 5 ton and the Wright 3 ton, overhead cranes did not have all functional operating mechanisms inspected on a frequency of daily to monthly intervals.
Recent events (2)
- — I (S) $1365
- — Z (S) $2100
1910.212 A01
- Issued
- Apr 10, 2012
- Abate by
- May 1, 2012
- Penalty
- Initial $2,800 · Current $1,820 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On 1/30/2012, the following machines in the tool room were not properly safeguarded. a) The two Bridgeport milling machines did not have rotating chuck guarding. b) The Carlton and the Hercules radial arm drill presses did not have rotating chuck guarding. c) The DoAll horizontal bandsaw had 3" of the used portion of the saw blade under the platen that was not guarded.
Recent events (2)
- — I (S) $1820
- — Z (S) $2800
1910.217 C01 I
- Issued
- Apr 10, 2012
- Abate by
- May 1, 2012
- Penalty
- Initial $3,500 · Current $2,275 Reduced
General-duty citation text
29 CFR 1910.217(c)(1)(i): The employer did not provide and ensure the usage of point of operation guards or properly applied point of operation devices on every operation performed on mechanical power press(es): The following mechanical powered punch presses in the press room had inadequate guarding. a) The #15 Bliss press had a side opening of 32" by 33". b) The #1 Cleveland press had a side opening of 10" by 11". c) The #2 and #3 Danly presses were open at the back sides.
Recent events (2)
- — I (S) $2275
- — Z (S) $3500
1910.217 E01 I
- Issued
- Apr 10, 2012
- Abate by
- May 1, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.217(e)(1)(i): A program of periodic and regular inspections of mechanical power press(es) was not established and followed to insure that all parts, auxiliary equipment and safeguards were in a safe operating condition and adjustment: On and before 1/30/2012, the 12 mechanical power presses operating in the press room did not receive a regular inspection of the machinery componets and safeguarding.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B01
- Issued
- Apr 10, 2012
- Abate by
- Apr 17, 2012
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1): On 1/30/2012, the electrical distribution panel in the basement area used for lighting, receptacles, lift and compressor had 9 overcurrent devices that were taped in the on position.
Recent events (2)
- — I (S) $3500
- — Z (S) $3500
1910.303 B02
- Issued
- Apr 10, 2012
- Abate by
- Apr 17, 2012
- Penalty
- Initial $2,800 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On 1/30/2012, at the Verson 21 press there was an unsecured electrical receptacle junction box with knockouts, attached to an electrical flexible cord. NOTE: Knockout boxes were designed to be secured to a fixed/permanent structure. When knockout boxes are used on the ends of flexible cords, employees gripping the box to attach or disconnect a plug may dislodge the circular scored metal portion in the box wall causing it to come in contact with the hot terminal. The result may lead to an electric shock.
Recent events (2)
- — I (S) $0
- — Z (S) $2800
1910.305 B01 I
- Issued
- Apr 10, 2012
- Abate by
- May 1, 2012
- Penalty
- Initial $2,100 · Current $2,100
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering boxes, cabinets, or fittings were not protected from abrasions: On 1/30/2012, at the Danly 16 press, the push button pedestal had electrical wiring flexible conduit that was damaged and open with wiring that was not protected.
Recent events (2)
- — I (S) $2100
- — Z (S) $2100
1910.305 B02 I
- Issued
- Apr 10, 2012
- Penalty
- Initial $2,380 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose: On 1/30/2012, in the basement on the east wall, the electrical service box for the outside flag pole had the cover open with the wiring exposed.
Recent events (2)
- — I (S) $0
- — Z (S) $2380
1910.147 C06 I
- Issued
- Apr 10, 2012
- Abate by
- May 1, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: On and before 1/30/2012, the employer did not conduct a lockout tagout periodic inspection of machines such as but not limited to mechanical powered punch presses.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B01 II
- Issued
- Apr 10, 2012
- Abate by
- Apr 17, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed: On 1/30/2012, there were two electrical disconnect switches in the basement on the east wall with three unused openings.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Artisan Industries INC.
View Artisan Industries INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332999)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331903260.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.