Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,124Inspections Most recent open 2026-08-25 Last loaded 2026-08-28

OSHA Inspection: ADVANCED EDUCATIONAL PRODUCTS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ADVANCED EDUCATIONAL PRODUCTS, INC. in 2495 MAIN STREET, SUITE230, BUFFALO, NY 14214 (NAICS 424120). OSHA activity number 331907378.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Advanced Educational Products, INC. for free Get an email when a new federal OSHA severe-injury report for Advanced Educational Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2495 MAIN STREET, SUITE230
City
BUFFALO
State
NY
ZIP
14214
Mailing
2495 MAIN STREET, SUITE230, BUFFALO, NY 14214
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424120
Employees
65
Ownership type
Private (A)

5 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 5 3 instances 4 exposed
Issued
Feb 9, 2012
Abate by
Feb 14, 2012
Penalty
Initial $2,975 · Current $1,500 Reduced
29 CFR 1910.303(g)(2)(i):  Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures, covers or by other suitable means:    a) On or about 02-02-12, In the IT room:  An  Oster microwave oven and a  Gold Star refrigerator were connected to a 120 volt AC power via an extension cord.  The extension cord was plugged into a receptacle in a 4 receptacle obox that lacked a cover, exposing live parts.    b) On or about 02-02-12, In the Warehouse: The cover on the pallet wrapper control box was left off exposing electrical parts. Although the disconnect for the pallet wrapper was in the "off" position, there was  no lock or tag on the handle of the disconnect switch to prevent someone from moving the switch to the "on" position, thereby energizing the parts in the control box.    c) On or about 02-02-12, in the Warehouse Entrance Area: An rectangular opening in the wall containing energized conductors at 120 volts-ac with only "wire nuts" covering the live parts lacked a cover.      Abatement certification required.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2975

1910.305 B01

Serious 1 instance 1 exposed
Issued
Feb 9, 2012
Abate by
Feb 14, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1): Unused openings in boxes, cabinets, or fittings were not effectively closed:      a) On or about 02-02-12, In the Warehouse Assembly Area:    A "knockout plug" on a 4-receptacle outlet box was missing.    Abatement certification required.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.304 G05

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 9, 2012
Abate by
Feb 14, 2012
Penalty
Initial $2,380 · Current $1,500 Reduced
29 CFR 1910.304(g)(5):     Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.    a) On or about 02-02-12, In the IT room:  An  Oster microwave oven and a  Gold Star refrigerator were connected to  20 volt AC power via an extension cord.  The plug on the extension cord lacked a ground prong.    Abatement certification required.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2380

1910.305 G01 IV D

Serious Gravity 1 1 instance 3 exposed
Issued
Feb 9, 2012
Abate by
Feb 14, 2012
Penalty
Initial $1,785 · Current $1,200 Reduced
29 CFR 1910.305(g)(1)(iv)(D):     Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, Flexible cords and/ or cables were used where attached to building surfaces.    a. On or about 02-02-12, in the IT Room:  An Oster microwave and a Gold Star refrrigerator were connected to 120 volt-ac power via an extension cord which was stapled to the wall around and over a doorway opening.     Abatement Certification Required
Recent events (2)
  • · I (S) $1200
  • · Z (S) $1785

1910.37 B04

Other-than-serious 1 instance 1 exposed
Issued
Feb 9, 2012
Abate by
Feb 14, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4):    Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:    a. On or about 02-02-12, in the back part of the warehouse: The way to get out of the warehouse to the main hallway on the second floor of the building was not immediately apparent.  Two additional signs were needed.    Abatement Certification Required