VERSAILLES, OH ·
OSHA Inspection: KING'S COMMAND FOODS, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of KING'S COMMAND FOODS, INC. in 770 N. CENTER ST., VERSAILLES, OH 45380 (NAICS 311999). OSHA activity number 331908632.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KING'S COMMAND FOODS, INC.
- Site address
- 770 N. CENTER ST.
- City
- VERSAILLES
- State
- OH
- ZIP
- 45380
- Mailing
- 770 N. CENTER ST., VERSAILLES, OH 45380
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311999
- Employees
- 25
- Ownership type
- Private (A)
Citations
6 citations on file for this inspection.
1910.23 C01
- Issued
- Mar 14, 2012
- Abate by
- Apr 25, 2012
- Penalty
- Initial $2,550 · Current $500 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Every open-sided floor or platform 4 feet or more above adjacent floor or ground level shall be guarded by a standard railing (or the equivalent as specified in paragraph (e)(3) of this section) on all open sides except where there is entrance to a ramp, stairway, or fixed ladder. In the Grinding Room at the Blender Machine, an employee was exposed to a fall hazard from an inadequate guardrail system on the open-sided floor of the working platform from a top rail chain having a sag of 12 inches and no midrail.
Recent events (2)
- · I (O) $500
- · Z (S) $2550
1910.147 C06 I
- Issued
- Mar 14, 2012
- Abate by
- Apr 11, 2012
- Penalty
- Initial $2,550 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer shall conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed. Periodic inspections of the Company's energy control procedures had not been conducted on at least an annual basis.
Recent events (2)
- · I (S) $1785
- · Z (S) $2550
1910.147 D06
- Issued
- Mar 14, 2012
- Abate by
- Apr 11, 2012
- Penalty
- Initial $2,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(d)(6): Verification of isolation. Prior to starting work on machines or equipment that have been locked out or tagged out, the authorized employee shall verify that isolation and deenergization of the machine or equipment have been accomplished. On or about January 24, 2012, in the Grinding Room, an employee was tearing down the Hydroflaker and did not verify the isolation after affixing the lockout device on the electrical energy source by trying to start the machine with the on button.
Recent events (2)
- · I (S) $0
- · Z (S) $2550
1910.332 B01
- Issued
- Mar 14, 2012
- Abate by
- Apr 11, 2012
- Penalty
- Initial $2,550 · Current $500 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments. Employees performing energized electrical work were inadequately trained on safety-related work practices in that affected employes were unfamiliar with when and what PPE to wear when performing energized electrical work.
Recent events (2)
- · I (O) $500
- · Z (S) $2550
1910.137 B02 VIII
- Issued
- Mar 14, 2012
- Abate by
- Apr 11, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-5 and Table I-6. Insultated rubber gloves used by employees performing energized electrical work had not been inspected based on the test voltage and interval between tests.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.178 L04 III
- Issued
- Mar 14, 2012
- Abate by
- Apr 11, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance shall be conducted at least once every three years. Operators of powered industrial trucks, sit-down forklift and power pallet truck, had not received an evaluation of their operator performance once every three years.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at King'S Command Foods, INC.
View King'S Command Foods, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311999)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 331908632.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.