MILWAUKEE, WI —
OSHA Inspection: ACRO METAL STAMPING CO.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ACRO METAL STAMPING CO. in 2200 W. CORNELL ST., MILWAUKEE, WI 53209 (NAICS 332116). OSHA activity number 331908897.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ACRO METAL STAMPING CO.
- Site address
- 2200 W. CORNELL ST.
- City
- MILWAUKEE
- State
- WI
- ZIP
- 53209
- Mailing
- 2200 W. CORNELL ST., MILWAUKEE, WI 53209
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332116
- Employees
- 20
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.22 A01
- Issued
- May 21, 2012
- Abate by
- Jun 30, 2012
- Penalty
- Initial $1,377 · Current $700 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition. (a) Coil straighteners exposed press operators and other employees to a tripping and cut hazard in-that the coils were not identified or cordoned off to prevent employees from inadvertently walking into the coils being feed into presses.
Recent events (2)
- — I (S) $700
- — Z (S) $1377
1910.305 B01 I
- Issued
- May 21, 2012
- Abate by
- May 22, 2012
- Penalty
- Initial $2,295 · Current $1,300 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors enter boxes, cabinets, or fittings were not effectively closed. (a) Electrical boxes located on press number 3 (Niagra 90 ton press) did not have the openings through which electrical wiring entered the box(es) effectively closed. The flexible metalic cable through which the conductors were run, was broken away from the connection fitting, exposing the conductors. This exposed employees to an electrical shock hazard.
Recent events (2)
- — I (S) $1300
- — Z (S) $2295
1910.305 B02 I
- Issued
- May 21, 2012
- Abate by
- May 22, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose. (a) Electrical box located on press number four (4) (Niagra 150 ton press) did not have a cover, exposing electrical wiring, exposing operator(s) and other employees to an electrical shock hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C06 II
- Issued
- May 21, 2012
- Abate by
- Jun 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(ii): The employer shall certify that the periodic inspections have been performed. The certification shall identify the machine or equipment on which the energy control procedure was being utilized, the date of the inspection, the employees included in the inspection, and the person performing the inspection. (a) The employer did not certify in writing that a periodic inspection had been accomplished for each employee authorized to perform lockout.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.178 L04 III
- Issued
- May 21, 2012
- Abate by
- Jun 5, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operators performance was not conducted at least once every 3 years (a) Powered industrial truck operators have not been evaluated every three years. Training was last conducted for forklift operators in year 2007.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Acro Metal Stamping CO.