Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: SANDPOINT GAS N GO & LUBE CNTR INC. DBA SHELL RAPID LUBE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SANDPOINT GAS N GO & LUBE CNTR INC. DBA SHELL RAPID LUBE in 404 LARCH ST., SANDPOINT, ID 83864 (NAICS 811191). OSHA activity number 332425974.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sandpoint GAS N GO & Lube Cntr INC. DBA Shell Rapid Lube for free Get an email when a new federal OSHA severe-injury report for Sandpoint GAS N GO & Lube Cntr INC. DBA Shell Rapid Lube is published. One employer, no account, unsubscribe in one click.
Site address
404 LARCH ST.
City
SANDPOINT
State
ID
ZIP
83864
Mailing
830 N. 5TH AVE., SANDPOINT, ID 83864
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811191
Employees
3
Ownership type
Private (A)

7 citations on file for this inspection.

1910.23 A05

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 16, 2012
Abate by
Apr 23, 2012
Penalty
Initial $1,800 · Current $500 Reduced
29 CFR 1910.23(a)(5): Every pit and floor opening was not adequately guarded by standard railing or any other effected means    (a) In the shop: On or about February 24, 2012, and at times prior thereto, the openings into the service pits were not guarded against employees falling into them when there are not vehicles being serviced.    Note: Abatement certificaiton is required for this item.
Recent events (2)
  • · I (S) $500
  • · Z (S) $1800

1910.305 J01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 16, 2012
Abate by
Apr 23, 2012
Penalty
Initial $3,000 · Current $500 Reduced
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact:    (a) In the pit: On or about February 24, 2012, and at times prior thereto, the cover was removed from a flourescent light fixture in the service pit exposing employees to the live conductors inside.    Note: Abatement certification is required for this item.
Recent events (2)
  • · I (S) $500
  • · Z (S) $3000

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 16, 2012
Abate by
Apr 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    (a) In the Shop: On or about February 24, 2012, and at times prior thereto, the outer insulation had pulled away from the plug end of an extension cord.    Note: Abatement certification is required for this item.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.334 A02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 16, 2012
Abate by
Apr 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service:    (a) In the Shop: On or about February 24, 2012, and at times prior thereto, an extension cord in the Northeast corner of the shop had cuts in the outer insulation and was still being used.    Note: Abatement certification is required for this item.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.334 A03 II

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 16, 2012
Abate by
Apr 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(3)(ii): Attachment plugs and receptacles were connected or altered in a manner which prevented proper continuity of the electric equipment grounding conductor at the point where plugs were attached to receptacles:    (a) In the Shop: On or about February 24, 2012, and at times prior thereto, an extension cord in the north east corner of the shop was missing the grounding prong.    Note: Abatement certification is required for this item.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.157 E02

Other-than-serious 2 instances 2 exposed
Issued
Apr 16, 2012
Abate by
Apr 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:    (a) In the shop: On or about February 24, 2012, and at times prior thereto, the fire extinguisher in the northeast corner of the shop had not been visually inspected.    (b) In the Service Pit: On or about February 24, 2012, and at times prior thereto, the fire extinguisher by the stairs had not been visually inspected.    Note: Abatement certification is required for this item.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.157 E03

Other-than-serious 1 instance 2 exposed
Issued
Apr 16, 2012
Abate by
Apr 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:    (a) In the Shop: On or about February 24, 2012, and at times prior thereto, the fire extinguisher in the northeast corner of the shop was past its annual maintenance check.    Note: Abatement certification is required for this item.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 332425974.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.