PEWAUKEE, WI —
OSHA Inspection: STAY-LITE LIGHTING, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of STAY-LITE LIGHTING, INC. in W233 N2800 ROUNDY CIRCLE WEST SUITE 100, PEWAUKEE, WI 53072 (NAICS 238210). OSHA activity number 332792613.
Where did this inspection happen?
- Establishment
- STAY-LITE LIGHTING, INC.
- Site address
- W233 N2800 ROUNDY CIRCLE WEST SUITE 100
- City
- PEWAUKEE
- State
- WI
- ZIP
- 53072
- Mailing
- W233 N2800 ROUNDY CIRCLE WEST SUITE 100, PEWAUKEE, WI 53072
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 33
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.137 B02 VIII
- Issued
- Penalty
- Initial $3500.00 · Current $3500.00
General-duty citation text
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6: (a) Lighting Technicians used Salisbury rubber insulating gloves, Class 00, Type II gloves rated to 500 volts AC when working on energized circuits that had not been electrically tested within the past 6 months to verify integrity of insulating properties. This exposed Lighting Technicians to an electrical shock hazard.
Recent events (2)
- — I (O) $3500
- — Z (S) $3500
1910.333 A
- Issued
- Abate by
- Penalty
- Initial $4900.00 · Current $4500.00 Reduced
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: (a) Lighting Technician(s) did not implement electrical safety-related work practices when performing lighting ballast replacement, exposing them to a 277 Volt AC electrical shock and burn hazard, from direct and indirect electrical contacts. Electrical safety-related work practices to be employed, include, but is not limited to electrical hazard evaluation, testing and verification procedures, lock out of electrical circuits, and use of personal protective equipment.
Recent events (2)
- — I (O) $4500
- — Z (S) $4900
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $4900.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: (a) Employee(s) performing lighting ballast replacement, did not wear electrically rated insulating gloves exposing them to electrical shock hazards.
Recent events (2)
- — I (O) $0
- — Z (S) $4900
More inspections at STAY-LITE LIGHTING, INC.
SALEM, WI—2013-05-07 00:00:00
STAY-LITE LIGHTING INC.
View STAY-LITE LIGHTING, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
SOUTH FULTON, GA—2026-07-10
REEDWICK, LLC
NIAGARA FALLS, NY—2026-07-10
GAINES ELECTRICAL CONTRACTING, INC.
OGDENSBURG, NY—2026-07-10
S & L ELECTRIC, INC.
BOISE, ID—2026-07-09
POWERHOUSE ELECTRIC INC.
LYNCHBURG, VA—2026-07-09
WHITE ELECTRICAL SERVICES LLC
More inspections in WI
MUSCODA, WI—2026-07-10
SCOT INDUSTRIES, INC