Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: STAY-LITE LIGHTING, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of STAY-LITE LIGHTING, INC. in W233 N2800 ROUNDY CIRCLE WEST SUITE 100, PEWAUKEE, WI 53072 (NAICS 238210). OSHA activity number 332792613.

Watch Stay-Lite Lighting, INC. — free Get an email when a new federal OSHA severe-injury report for Stay-Lite Lighting, INC. is published. One employer, no account, unsubscribe in one click.
Site address
W233 N2800 ROUNDY CIRCLE WEST SUITE 100
City
PEWAUKEE
State
WI
ZIP
53072
Mailing
W233 N2800 ROUNDY CIRCLE WEST SUITE 100, PEWAUKEE, WI 53072
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
33
Ownership type
A

3 citations on file for this inspection.

1910.137 B02 VIII

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $3500.00 · Current $3500.00
29 CFR 1910.137(b)(2)(viii):     Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6:    (a) Lighting Technicians used Salisbury rubber insulating gloves, Class 00, Type II gloves rated to 500 volts AC when working on energized circuits that had not been electrically tested within the past 6 months to verify integrity of insulating properties. This exposed Lighting Technicians to an electrical shock hazard.
Recent events (2)
  • — I (O) $3500
  • — Z (S) $3500

1910.333 A

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $4500.00 Reduced
29 CFR 1910.333(a):     Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:    (a) Lighting Technician(s) did not implement electrical safety-related work practices when performing lighting ballast replacement, exposing them to a 277 Volt AC electrical shock and burn hazard, from direct and indirect electrical contacts. Electrical safety-related work practices to be employed, include, but is not limited to electrical hazard evaluation, testing and verification procedures, lock out of electrical circuits, and use of personal protective equipment.
Recent events (2)
  • — I (O) $4500
  • — Z (S) $4900

1910.335 A01 I

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $0.00 Reduced
29 CFR 1910.335(a)(1)(i):     Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:    (a) Employee(s) performing lighting ballast replacement, did not wear electrically rated insulating gloves exposing them to electrical shock hazards.
Recent events (2)
  • — I (O) $0
  • — Z (S) $4900

View STAY-LITE LIGHTING, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332792613.