Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WE ENERGIES

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of WE ENERGIES in 11060 S. CHICAGO RD., OAK CREEK, WI 53154 (NAICS 221112). OSHA activity number 332800556.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch WE Energies — free Get an email when a new federal OSHA severe-injury report for WE Energies is published. One employer, no account, unsubscribe in one click.
Establishment
WE ENERGIES
Site address
11060 S. CHICAGO RD.
City
OAK CREEK
State
WI
ZIP
53154
Mailing
11060 S. CHICAGO RD., OAK CREEK, WI 53154
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221112
Employees
280
Ownership type
A

3 citations on file for this inspection.

1910.269 D06 III

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jun 19, 2012
Abate by
Jul 11, 2012
Penalty
Initial $3,400 · Current $0 Reduced
29 CFR 1910.269(d)(6)(iii):   All energy isolating devices needed to control the energy to the machine or equipment were not physically located and/or operated in such a manner as to isolate the machine or equipment from energy sources:  (a) On or about February 29, 2012; employees were performing work on a steam conditioning valve, Unit 7, to remove a diaphragm to repair Unit 6.  De-energization of all energy sources, such as but not limited to spring tension, was not performed exposing employees to struck-by hazards.    IN THE ALTERNATIVE:    29 CFR 1910.147(d):   The established procedure for the application of energy control (the lockout or tagout procedures) did not cover the actions listed in and was not done in sequence as required by 29 CFR 1910.147(d)(1)-(6):  (a) On or about February 29, 2012; employees were performing work on a steam conditioning valve, Unit 7, to remove a diaphragm to repair Unit 6.  De-energization of all energy sources, such as but not limited to spring tension, was not performed exposing employees to struck-by hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3400

1910.269 D06 V

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 19, 2012
Abate by
Jul 11, 2012
Penalty
Initial $0 · Current $2,000
29 CFR 1910.269(d)(6)(v):   Following the application of lockout or tagout devices to energy isolating devices, all potentially hazardous stored or residual energy was not relieved, disconnected, restrained, or otherwise rendered safe:  (a)  On or about February 29, 2012; employees were performing work on the Unit 7 steam conditioning valve and failed to relieve the spring tension exposing employees to struck-by hazards.    IN THE ALTERNATIVE    29 CFR 1910.147(d)(5)(i):   All potentially hazardous stored or residual energy was not relieved, disconnected, restrained or otherwise rendered safe after the application of lockout or tagout devices to energy isolating devices:  (a)  On or about February 29, 2012; employees were performing work on the Unit 7 steam conditioning valve and failed to relieve the spring tension exposing employees to struck-by hazards.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $0

1910.269 D02 V E

Deleted Other-than-serious 1 instance 3 exposed
Issued
Jun 19, 2012
Abate by
Aug 1, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.269(d)(2)(v)[E]:    The periodic inspection certification of the energy control procedures did not contain the required documentation to identify the machine or equipment on which the energy control procedure was being used, the date of the inspection, the employees included in the inspection, and the person performing the inspection.  (a) The employer protective tag audit certification did not include the names of the employee(s) included in the inspection.    IN THE ALTERNATIVE    29 CFR 1910.147(c)(6)(ii):   The periodic inspection certification of energy control procedures did not contain the required documentation on identification of the machine or equipment, inspection date, employees included, and the person performing the inspection.  (a) The employer protective tag audit certification did not include the names of the employee(s) included in the inspection.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View WE Energies's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332800556.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.