Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: HUPP STIVERSON COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of HUPP STIVERSON COMPANY in 4300 WEST PIKE, ZANESVILLE, OH 43701 (NAICS 339995). OSHA activity number 332800861.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hupp Stiverson Company — free Get an email when a new federal OSHA severe-injury report for Hupp Stiverson Company is published. One employer, no account, unsubscribe in one click.
Site address
4300 WEST PIKE
City
ZANESVILLE
State
OH
ZIP
43701
Mailing
P.O. BOX 430, ZANESVILLE, OH 43702
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339995
Employees
22
Ownership type
A

4 citations on file for this inspection.

1910.178 L01 I

Serious Gravity 1 1 instance 6 exposed
Issued
Apr 9, 2012
Abate by
May 11, 2012
Penalty
Initial $1,800 · Current $1,260 Reduced
29 CFR 1910.178(l)(1)(i):     The employer shall ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l).    Hupp Stiverson Company - 4300 West Pike, Zanesville Ohio establishment; as of and prior to March 6, 2012, the employer had not established an operator training program for forklift operators consisting of formal instruction, practical training and operator evaluation. Employees utilize forklifts to move burial vaults from the production area to the storage building on a routine basis.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $1800

1910.305 G02 II

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 9, 2012
Abate by
Apr 18, 2012
Penalty
Initial $3,000 · Current $2,100 Reduced
29 CFR 1910.305(g)(2)(ii):     Flexible cords may be used only in continuous lengths without splice or tap. Hard-service cord and junior hard-service cord No. 14 and larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced.    a. Hupp Stiverson Company - 4300 West Pike, Zanesville Ohio establishment; as of and prior to March 6, 2012; two extension cords were "daisy chained" to provide power for a light fixture on the mixer. The extension cords each have a makeshift splice that is not properly repaired or otherwise protected. This condition poses an increased risk for electrocution to employees with routine exposure from mixer operator, set up and cleaning duties.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $3000

1910.147 C07 I B

Other-than-serious 1 instance 1 exposed
Issued
Apr 9, 2012
Abate by
May 2, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i)(B):     Each affected employee shall be instructed in the purpose and use of the energy control procedure.    a.Hupp Stiverson Company - 4300 West Pike, Zanesville Ohio establishment; as of and prior to March 6, 2012, a laborer working in the burial vault manufacturing area had not received hazardous energy control (locout/tagout) training and/or instruction as an affected employee. The mixer is cleaned on a daily basis and has associated mechanical energy addressed by an energy control procedure.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.304 G05

Other-than-serious 1 instance 6 exposed
Issued
Apr 9, 2012
Abate by
Apr 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5):     Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.    a. Hupp Stiverson Company - 4300 West Pike, Zanesville Ohio establishment; as of and prior to March 6, 2012, a combination light switch and two receptacle outlet box had a broken ground pin stuck in the lower receptacle fixture.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332800861.