BROOKFIELD, MO —
OSHA Inspection: STANBURY UNIFORMS, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of STANBURY UNIFORMS, INC. in 108 STANBURY INDUSTRIAL DRIVE, BROOKFIELD, MO 64628 (NAICS 315211). OSHA activity number 332804244.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STANBURY UNIFORMS, INC.
- Site address
- 108 STANBURY INDUSTRIAL DRIVE
- City
- BROOKFIELD
- State
- MO
- ZIP
- 64628
- Mailing
- P.O. BOX 100, BROOKFIELD, MO 64628
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 315211
- Employees
- 131
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Apr 3, 2012
- Abate by
- Jul 30, 2012
- Penalty
- Initial $3,600 · Current $1,800 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Located on the manufacturing floor at Stanbury Uniforms are approximately 130 electrical drops which have been installed using 4 plex junction boxes which are not listed or labelled for this use. Junction boxes are designed for solid installation only. Abatement verification is required for this violation. The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
- — I (S) $1800
- — Z (S) $3600
1910.303 G01 II
- Issued
- Apr 3, 2012
- Abate by
- Apr 18, 2012
- Penalty
- Initial $3,600 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: (a) In the North Corner of the warehouse building, near the hat mold equipment, A Square D 440 volt load center and a Square D 220 volt load center were blocked by a welder and an unused vacuum mold press. Abatement verification is required for this violation. The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
- — I (O) $1000
- — Z (S) $3600
1910.305 G02 III
- Issued
- Apr 3, 2012
- Abate by
- Jul 30, 2012
- Penalty
- Initial $3,600 · Current $1,800 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) Located on the manufacturing floor at Stanbury Uniforms are approximately 130 electrical drops which have been installed using 4 plex junction boxes and flexible cable. Strain relief that would have prevented pull from being directly transmitted to joints or terminal screws was not provided. Abatement verification is required for this violation. The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
- — I (S) $1800
- — Z (S) $3600
More inspections at Stanbury Uniforms, INC.
View Stanbury Uniforms, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 315211)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332804244.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.