SAN DIEGO, CA ·
OSHA Inspection: U.S. DEPARTMENT OF VETERAN AFFAIRS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF VETERAN AFFAIRS in 3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161 (NAICS 622110). OSHA activity number 332811561.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. DEPARTMENT OF VETERAN AFFAIRS
- Site address
- 3350 LA JOLLA VILLAGE DRIVE
- City
- SAN DIEGO
- State
- CA
- ZIP
- 92161
- Mailing
- 3350 LA JOLLA VILLAGE DR., SAN DIEGO, CA 92161
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 4400
- Ownership type
- Federal government (D)
Citations
8 citations on file for this inspection.
1910.178 A04
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(a)(4): Modifications and additions which affect capacity and safe operation were performed by the customer or user without manufactures prior written approval. Capacity, operation, and maintenance instruction plates, tags or decals were not changed accordingly: On March 13, 2012, and at times prior thereto, where six foot extensions and a boom attachment were used, the employer did not get the manufacturers approval to be used with the forklifts.
Recent events (1)
- · Z (S) $0
1910.178 A05
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(a)(5): Where powered industrial trucks were equipped with front-end attachments other than factory installed attachments, the employer did not request that the truck be marked to identify the attachments and show the approximate weight of the truck and attachment combination at maximum elevation with the load laterally centered: On March 13, 2012, and at times prior thereto, where six foot extensions and a boom attachment were used for the forklifts, the forklifts did not have a name plate to indicate the truck's lifting capacity.
Recent events (1)
- · Z (S) $0
1910.212 A01
- Issued
- Apr 24, 2012
- Abate by
- Apr 26, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect the operator(s) and other employees from hazard(s) created by rotating parts: Building 2, Machine Shop: On March 13, 2012, and at times prior thereto, the rotating notched chuck on the Rockwell horizontal lathe was not provided with safeguarding to prevent unintentional contact.
Recent events (1)
- · Z (S) $0
1910.215 B09
- Issued
- Apr 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The guard for abrasive wheel machine where the operator stands in front of the machine was not constructed so that the peripheral protecting member could be adjusted to the constantly decreasing diameter of the wheel: Carpenter Shop: On March 13, 2012, and at times prior thereto, the Baldor bench grinder's adjustable tongue guard measured at one half inch from the abrasive wheel.
Recent events (1)
- · Z (S) $0
1910.253 B04 I
- Issued
- Apr 24, 2012
- Abate by
- Apr 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders: Cylinder Storage Area, West Loading Dock: On March 14, 2012, and at times prior thereto, four acetlyene cylinders where stored within five feet of approximately a dozen oxygen cylinders.
Recent events (1)
- · Z (S) $0
1910.303 B02
- Issued
- Apr 24, 2012
- Abate by
- May 1, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: HVAC/Equipment Shop: On March 13, 2012, and at times prior thereto, two power taps did not meet the specifications for use in a commerical/industrial location.
Recent events (1)
- · Z (S) $0
1910.303 E01 I
- Issued
- Apr 24, 2012
- Abate by
- May 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e)(1)(i): The manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product was not identified on electrical equipment: On March 13, 2012, and at times prior thereto, in the following locations, homemade electrical outlets were not descriptively marked; A. East loading dock by exit door: A fire alarm was energized by a homemade junction box. B. HVAC/Equipment Shop: A metal outlet box was covered with plastic outlet cover and energized a hot water dispenser.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV A
- Issued
- Apr 24, 2012
- Abate by
- May 1, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used for purposes prohibited by subparagraphs (a) through (f) of this paragraph: On March 13, 2012 and at times prior thereto, in the following locations, extension cords were being used in lieu of permanent wiring; A. East loading dock: To energize refrigerators during trouble shooting. B. HVAC/Equipment Shop, Lunch Area: To energize a fry-o-lator. C. Electrical Room B231: To energize the Wireguard System for the Community Living Center. D. Chemistry Lab, Rm 1242: One extension cord energized the OceanAire Portable AC Unit and another energized a UPS battery back up system. The U.S. Department of Veterans Affairs was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.305(g)(1)(iv)(A) which was contained in OSHA Inspection Number 315053777, Citation Number 01, Item Number 006, issued on 03/07/2012, with respect to a workplace located at 5901 E 7th Street, Long Beach, CA 90822, which became final order on 03/29/2011.
Recent events (1)
- · Z (R) $0
More inspections at U.S. Department of Veteran Affairs
View U.S. Department of Veteran Affairs's full OSHA safety record →
More inspections in this industry (NAICS 622110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 332811561.