OSHA Inspection: T. MARZETTI COMPANY - ALLEN DIVISION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of T. MARZETTI COMPANY - ALLEN DIVISION in 1709 FRANK ROAD, COLUMBUS, OH 43216 (NAICS 311999). OSHA activity number 332821040.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch T. Marzetti Company - Allen Division for free Get an email when a new federal OSHA severe-injury report for T. Marzetti Company - Allen Division is published. One employer, no account, unsubscribe in one click.
Site address
1709 FRANK ROAD
City
COLUMBUS
State
OH
ZIP
43216
Mailing
P.O. BOX 453, COLUMBUS, OH 43216
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311999
Employees
120
Ownership type
Private (A)

2 citations on file for this inspection.

1910.303 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 25, 2012
Penalty
Initial $4,125 · Current $2,475 Reduced

Hazardous substances 8870

29 CFR 1910.303(b)(1)(ii): Mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided;    T. Marzetti Company - Allen Division, 1709 Frank Road, Columbus Ohio establishment: As of and prior to March 21, 2012, in the Sour Cream Kitchen at the Grade A Homogenizer there was damaged two inch conduit designed to enclose the 3-phase electrical power supply contained within. Due to this condition, personnel at the operating panel/controls have an increased risk for electrocution related to this electrical shock hazard.
Recent events (2)
  • · I (S) $2475
  • · Z (S) $4125

1910.305 G01 IV B

Other-than-serious 2 instances 10 exposed
Issued
Apr 25, 2012
Penalty
Initial $0 · Current $0

Hazardous substances 8870

29 CFR 1910.305(g)(1)(iv)(B): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: where run through holes in walls, ceilings, or floors;    T. Marzetti Company - Allen Division, 1709 Frank Road, Columbus Ohio establishment: As of and prior to March 21, 2012, in the mixer area there were two electric power supply cords for mixing equipment run through the ceiling without use of junction box or other equipment to protect from abrasion and/or other damage. This poses an increased risk of electrocution for operators of this equipment.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 332821040.