PASSAIC, NJ —
OSHA Inspection: EFS STRUCTURES
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of EFS STRUCTURES in 151 RANDOLPH AVE, PASSAIC, NJ 07055 (NAICS 332999). OSHA activity number 332826643.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EFS STRUCTURES
- Site address
- 151 RANDOLPH AVE
- City
- PASSAIC
- State
- NJ
- ZIP
- 07055
- Mailing
- 780 ELK RIDGE LANDING SUITE 101, LINTHICUM, MD 21090
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332999
- Employees
- 30
- Ownership type
- A
Citations
4 citations on file for this inspection.
5(a)(1)
- Issued
- Sep 7, 2012
- Penalty
- Initial $3,000 · Current $3,000
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to a struck by falling objects hazard: a) Secondary building: The Hook of a 2 Ton electric hoist was not equipped with a safety latch, on or about 3/23/2012.
Recent events (1)
- — Z (S) $3000
1910.219 E01 I
- Issued
- Sep 7, 2012
- Penalty
- Initial $2,400 · Current $2,400
General-duty citation text
29 CFR 1910.219(e)(1)(i): Horizontal belts which had both runs 42 inches or less from the floor level were not fully enclosed by guards conforming to requirements specified in 29 CFR 1910.219(m) and (o): a) Main Building: Employeew were exposed to a caught-in-between hazard by working with a compressor without guards, on or about 3/23/2012
Recent events (1)
- — Z (S) $2400
1910.303 B02
- Issued
- Sep 7, 2012
- Penalty
- Initial $4,200 · Current $4,200
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Driveway: Employees were using a junction box designed for interior wall mounting use, connected to flexible cord to power cutting equipment, on or about 3/23/2012.
Recent events (1)
- — Z (S) $4200
1910.304 G05
- Issued
- Sep 7, 2012
- Penalty
- Initial $4,200 · Current $4,200
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective. a) Secondary building: Employees were operating a 2 ton electric hoist with removed ground pin, on or about 3/23/2012.
Recent events (1)
- — Z (S) $4200
More inspections at EFS Structures
View EFS Structures's full OSHA safety record →
More inspections in this industry (NAICS 332999)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332826643.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.