Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EFS STRUCTURES

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of EFS STRUCTURES in 151 RANDOLPH AVE, PASSAIC, NJ 07055 (NAICS 332999). OSHA activity number 332826643.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch EFS Structures — free Get an email when a new federal OSHA severe-injury report for EFS Structures is published. One employer, no account, unsubscribe in one click.
Establishment
EFS STRUCTURES
Site address
151 RANDOLPH AVE
City
PASSAIC
State
NJ
ZIP
07055
Mailing
780 ELK RIDGE LANDING SUITE 101, LINTHICUM, MD 21090
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332999
Employees
30
Ownership type
A

4 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 7, 2012
Penalty
Initial $3,000 · Current $3,000
OSH ACT of 1970 Section (5)(a)(1):     The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to a struck by falling objects hazard:    a) Secondary building: The Hook of a 2 Ton electric hoist was not equipped with a safety latch, on or about 3/23/2012.
Recent events (1)
  • — Z (S) $3000

1910.219 E01 I

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 7, 2012
Penalty
Initial $2,400 · Current $2,400
29 CFR 1910.219(e)(1)(i):     Horizontal belts which had both runs 42 inches or less from the floor level were not fully enclosed by guards conforming to requirements specified in 29 CFR 1910.219(m) and (o):    a) Main Building: Employeew were exposed to a caught-in-between hazard by working with a compressor without guards, on or about 3/23/2012
Recent events (1)
  • — Z (S) $2400

1910.303 B02

Serious Gravity 10 1 instance 3 exposed
Issued
Sep 7, 2012
Penalty
Initial $4,200 · Current $4,200
29 CFR 1910.303(b)(2):     Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) Driveway: Employees were using a junction box designed for interior wall mounting use, connected to flexible cord to power cutting equipment, on or about 3/23/2012.
Recent events (1)
  • — Z (S) $4200

1910.304 G05

Serious Gravity 10 1 instance 5 exposed
Issued
Sep 7, 2012
Penalty
Initial $4,200 · Current $4,200
29 CFR 1910.304(g)(5):     The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective.    a) Secondary building: Employees were operating a 2 ton electric hoist with removed ground pin, on or about 3/23/2012.
Recent events (1)
  • — Z (S) $4200

View EFS Structures's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332826643.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.