AUBURN, WA —
OSHA Inspection: FEDERAL AVIATION ADMINISTRATION SEATTLE TECHNICAL OPERATIONS SUPPORT CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FEDERAL AVIATION ADMINISTRATION SEATTLE TECHNICAL OPERATIONS SUPPORT CENTER in 3101 AUBURN WAY SOUTH, AUBURN, WA 98092 (NAICS 561210). OSHA activity number 332829076.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 3101 AUBURN WAY SOUTH
- City
- AUBURN
- State
- WA
- ZIP
- 98092
- Mailing
- 3101 AUBURN WAY SOUTH, AUBURN, WA 98092
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561210
- Employees
- 196
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.23 A02
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(a)(2): Ladderway floor opening(s) or platform(s) were not guarded by a standard railing with standard toeboard(s) on all exposed sides (except at the entrance to opening) with passage through the railing either provided with a swinging gate or so offset that a person could walk directly into the opening: a) Evapco Cooling Towers, where the guardrail at the landing platform for each cooling tower lacked an intermediate rail.
Recent events (1)
- — Z (S) $0
1910.147 C06 I
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: a) Facility, where employees performed preventative maintenance and repair on equipment such as, but not limited to, air compressors. An annual review of the lockout tagout program had not been conducted.
Recent events (1)
- — Z (S) $0
1910.179 B05
- Issued
- Apr 24, 2012
- Abate by
- Jun 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.179(b)(5): The rated load of crane(s) was not plainly marked on each side of the crane: a) Generator Room #104, where the beam supporting the overhead under hung crane was not marked with a load rating.
Recent events (1)
- — Z (S) $0
1910.305 J01 I
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact: a) Light fixtures equipped with unguarded single bulbs included: 1. Garage Painting Supplies Storage Closet, where an unguarded bulb measured 7 feet 5 inches above floor level. 2. Garage Electrical Supplies Storage Closet, where an unguarded bulb measured 7 feet 5 inches above floor level.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Condenser Water Pump Building, where an extension cord with a male plug was wired into a junction box and utilized to supply power to the permanently installed 1 Ton Man Guard overhead hoist. The Federal Aviation Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 106705, citation no. 2, item no. 4, issued on September 30, 2011 with respect to a workplace at Renton, WA. The Federal Aviation Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 106581, citation no. 3, item no. 3, issued on September 30, 2011 with respect to a workplace at Renton, WA.
Recent events (1)
- — Z (R) $0
1910.23 E01
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(e)(1): The railing did not consist of top rail, intermediate rail, and posts: a) Refuse Area, where the railing on the stairway located adjacent to the dumpster was not equipped with midrails.
Recent events (1)
- — Z (O) $0
1910.157 C01
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a) Second Floor, where fire extinguishers including but, not limited to, the Simplex Grinnell fire extinguishers mounted in the East and West Conference Rooms were not identified.
Recent events (1)
- — Z (O) $0
1910.159 C10
- Issued
- Apr 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained: a) Room 110-F Storage, where boxes stored on the top shelf measured approximately 6 inches below the automatic sprinkler head.
Recent events (1)
- — Z (O) $0
1910.303 G02 I D
- Issued
- Apr 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29CFR 1910.303(g)(2)(i)(D): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by elevation of 2.44 m (8.0 ft) or more above the floor or other working surface: a) Florescent light fixtures equipped with unguarded bulbs included: 1. Auto Wing Basement 11-A Hallway, where the light fixture measured 7 feet above floor level. 2. Vault Room 120-A, where two light fixtures measured 7 feet above floor level.
Recent events (1)
- — Z (O) $0
More inspections at Federal Aviation Administration Seattle Technical Operations Support Center
More inspections in this industry (NAICS 561210)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332829076.