OSHA Inspection: FEDERAL AVIATION ADMINISTRATION SEATTLE TECHNICAL OPERATIONS SUPPORT CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FEDERAL AVIATION ADMINISTRATION SEATTLE TECHNICAL OPERATIONS SUPPORT CENTER in 3101 AUBURN WAY SOUTH, AUBURN, WA 98092 (NAICS 561210). OSHA activity number 332829076.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Federal Aviation Administration Seattle Technical Operations Support Center — free Get an email when a new federal OSHA severe-injury report for Federal Aviation Administration Seattle Technical Operations Support Center is published. One employer, no account, unsubscribe in one click.
Site address
3101 AUBURN WAY SOUTH
City
AUBURN
State
WA
ZIP
98092
Mailing
3101 AUBURN WAY SOUTH, AUBURN, WA 98092
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
196
Ownership type
D

9 citations on file for this inspection.

1910.23 A02

Serious Gravity 5 3 instances 20 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.23(a)(2): Ladderway floor opening(s) or platform(s) were not guarded by a standard railing with standard toeboard(s) on all exposed sides (except at the entrance to opening) with passage through the railing either provided with a swinging gate or so offset that a person could walk directly into the opening:    a)  Evapco Cooling Towers, where the guardrail at the landing platform for each cooling tower lacked an intermediate rail.
Recent events (1)
  • — Z (S) $0

1910.147 C06 I

Serious Gravity 5 1 instance 50 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    a) Facility, where employees performed preventative maintenance and repair on equipment such as, but not limited to, air compressors. An annual review of the lockout tagout program had not been conducted.
Recent events (1)
  • — Z (S) $0

1910.179 B05

Serious Gravity 5 1 instance 50 exposed
Issued
Apr 24, 2012
Abate by
Jun 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.179(b)(5): The rated load of crane(s) was not plainly marked on each side of the crane:    a) Generator Room #104, where the beam supporting the overhead under hung crane was not marked with a load rating.
Recent events (1)
  • — Z (S) $0

1910.305 J01 I

Serious Gravity 1 2 instances 50 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact:    a) Light fixtures equipped with unguarded single bulbs included:    1. Garage Painting Supplies Storage Closet, where an unguarded bulb measured 7 feet 5 inches above floor level.    2.  Garage Electrical Supplies Storage Closet, where an unguarded bulb measured 7 feet 5 inches above floor level.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Repeat Gravity 1 1 instance 50 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    a) Condenser Water Pump Building, where an extension cord with a male plug was wired into a junction box and utilized to supply power to the permanently installed 1 Ton Man Guard overhead hoist.    The Federal Aviation Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 106705, citation no. 2, item no. 4, issued on September 30, 2011 with respect to a workplace at Renton, WA.    The Federal Aviation Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 106581, citation no. 3, item no. 3, issued on September 30, 2011 with respect to a workplace at Renton, WA.
Recent events (1)
  • — Z (R) $0

1910.23 E01

Other-than-serious 1 instance 50 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.23(e)(1): The railing did not consist of top rail, intermediate rail, and posts:     a) Refuse Area, where the railing on the stairway located adjacent to the dumpster was not equipped with midrails.
Recent events (1)
  • — Z (O) $0

1910.157 C01

Other-than-serious 2 instances 196 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:    a) Second Floor, where fire extinguishers including but, not limited to, the Simplex Grinnell fire extinguishers mounted in the East and West Conference Rooms were not identified.
Recent events (1)
  • — Z (O) $0

1910.159 C10

Other-than-serious 1 instance 1 exposed
Issued
Apr 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained:    a) Room 110-F Storage, where boxes stored on the top shelf measured approximately 6 inches below the automatic sprinkler head.
Recent events (1)
  • — Z (O) $0

1910.303 G02 I D

Other-than-serious 2 instances 196 exposed
Issued
Apr 24, 2012
Penalty
Initial $0 · Current $0
29CFR 1910.303(g)(2)(i)(D): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by  elevation of 2.44 m (8.0 ft) or more above the floor or other working surface:    a) Florescent light fixtures equipped with unguarded bulbs included:    1. Auto Wing Basement 11-A Hallway, where the light fixture measured 7 feet above floor level.    2. Vault Room 120-A, where two light fixtures measured 7 feet above floor level.
Recent events (1)
  • — Z (O) $0

View Federal Aviation Administration Seattle Technical Operations Support Center's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332829076.