Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: US DEPARTMENT OF AGRICULTURE, FOREST SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of US DEPARTMENT OF AGRICULTURE, FOREST SERVICE in 1400 S. ERIE MAIN, TONOPAH, NV 89049 (NAICS 924120). OSHA activity number 332838713.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch US Department of Agriculture, Forest Service for free Get an email when a new federal OSHA severe-injury report for US Department of Agriculture, Forest Service is published. One employer, no account, unsubscribe in one click.
Site address
1400 S. ERIE MAIN
City
TONOPAH
State
NV
ZIP
89049
Mailing
P.O. BOX 3490, TONOPAH, NV 89049
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
12
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 2 instances 4 exposed
Issued
Jul 5, 2012
Abate by
Jul 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): An exit access was not at least 28 inches (71.1 cm) wide at all points and the width of the exit and exit discharge was not at least equal to the width of the exit access.    (a) At the admin office the exit access was 23 inches wide.  (b) At the wild life technician's office the exit access was 19.5 inches wide.
Recent events (1)
  • · Z (S) $0

1910.37 B02

Serious Gravity 1 1 instance 4 exposed
Issued
Jul 5, 2012
Abate by
Jul 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):   Each exit were not clearly visible and marked by a sign reading "Exit."    (a)  At the Tonopah Ranger Station facility, the south door exit was not marked "EXIT".
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 5, 2012
Abate by
Jul 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    (a) At the administrator's office, two Archer relocatable power taps were daisy chained.
Recent events (1)
  • · Z (S) $0

1910.303 F02

Serious Gravity 5 1 instance 4 exposed
Issued
Jul 5, 2012
Abate by
Jul 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):  Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.    (a) East of the South Door Exit, the electrical power panel was not labeled.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 12 exposed
Issued
Jul 5, 2012
Abate by
Jul 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A):   Flexible cords and cables were used as a substitute for the fixed wiring of a structure    (a) At the copy room, a relocatable power tap was mounted permanently beneath the Lucent Technologies terminal cabinet.
Recent events (1)
  • · Z (S) $0

1904.40 A

Other-than-serious 1 instance 4 exposed
Issued
Jul 5, 2012
Abate by
Jul 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours.    (a) At the Ranger Station, Tonopah, On or about 3/14/2012, the employer failed to provide copies of the injury and illness records to an authorized representative for fiscal year 2008, 2009, 2010.
Recent events (1)
  • · Z (O) $0

1910.253 B04 III

Other-than-serious 1 instance 4 exposed
Issued
Jul 5, 2012
Abate by
Jul 10, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii):   Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high.    (a)  At the Ranger Station warehouse/work shop, oxygen and acetylene cylinders not in used were stored together.
Recent events (1)
  • · Z (O) $0

View US Department of Agriculture, Forest Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 332838713.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.