TONOPAH, NV ·
OSHA Inspection: US DEPARTMENT OF AGRICULTURE, FOREST SERVICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of US DEPARTMENT OF AGRICULTURE, FOREST SERVICE in 1400 S. ERIE MAIN, TONOPAH, NV 89049 (NAICS 924120). OSHA activity number 332838713.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- US DEPARTMENT OF AGRICULTURE, FOREST SERVICE
- Site address
- 1400 S. ERIE MAIN
- City
- TONOPAH
- State
- NV
- ZIP
- 89049
- Mailing
- P.O. BOX 3490, TONOPAH, NV 89049
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 12
- Ownership type
- Federal government (D)
Citations
7 citations on file for this inspection.
1910.36 G02
- Issued
- Jul 5, 2012
- Abate by
- Jul 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): An exit access was not at least 28 inches (71.1 cm) wide at all points and the width of the exit and exit discharge was not at least equal to the width of the exit access. (a) At the admin office the exit access was 23 inches wide. (b) At the wild life technician's office the exit access was 19.5 inches wide.
Recent events (1)
- · Z (S) $0
1910.37 B02
- Issued
- Jul 5, 2012
- Abate by
- Jul 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit were not clearly visible and marked by a sign reading "Exit." (a) At the Tonopah Ranger Station facility, the south door exit was not marked "EXIT".
Recent events (1)
- · Z (S) $0
1910.303 B02
- Issued
- Jul 5, 2012
- Abate by
- Jul 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) At the administrator's office, two Archer relocatable power taps were daisy chained.
Recent events (1)
- · Z (S) $0
1910.303 F02
- Issued
- Jul 5, 2012
- Abate by
- Jul 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. (a) East of the South Door Exit, the electrical power panel was not labeled.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV A
- Issued
- Jul 5, 2012
- Abate by
- Jul 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure (a) At the copy room, a relocatable power tap was mounted permanently beneath the Lucent Technologies terminal cabinet.
Recent events (1)
- · Z (S) $0
1904.40 A
- Issued
- Jul 5, 2012
- Abate by
- Jul 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours. (a) At the Ranger Station, Tonopah, On or about 3/14/2012, the employer failed to provide copies of the injury and illness records to an authorized representative for fiscal year 2008, 2009, 2010.
Recent events (1)
- · Z (O) $0
1910.253 B04 III
- Issued
- Jul 5, 2012
- Abate by
- Jul 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high. (a) At the Ranger Station warehouse/work shop, oxygen and acetylene cylinders not in used were stored together.
Recent events (1)
- · Z (O) $0
More inspections at US Department of Agriculture, Forest Service
View US Department of Agriculture, Forest Service's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 332838713.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.