RAVENSDALE, WA ·
OSHA Inspection: U.S. ARMY CORPS OF ENGINEERS HOWARD HANSON DAM
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. ARMY CORPS OF ENGINEERS HOWARD HANSON DAM in 36932 SE GREEN RIVER HEADWORKS RD, RAVENSDALE, WA 98051 (NAICS 921190). OSHA activity number 333290708.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. ARMY CORPS OF ENGINEERS HOWARD HANSON DAM
- Site address
- 36932 SE GREEN RIVER HEADWORKS RD
- City
- RAVENSDALE
- State
- WA
- ZIP
- 98051
- Mailing
- 30532 SE MUD MOUNTAIN RD, ENUMCLAW, WA 98022
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 921190
- Employees
- 8
- Ownership type
- Federal government (D)
Citations
5 citations on file for this inspection.
1910.22 D01
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(d)(1): In every building or other structure, or part thereof, used for mercantile, business, industrial, or storage purposes, the loads approved by the building official were not marked in a conspicuous place in each space to which they related: a) Maintenance Shop, where the storage space located above the Clean Room was not equipped with a load rating plate.
Recent events (1)
- · Z (S) $0
1910.23 C
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(c): Every open-sided floor or platform 4 feet or more above adjacent floor or ground level was not guarded by a standard railing (or the equivalent as specified in paragraph (e)(3) of this section) on all open sides except where there is entrance to a ramp, stairway, or fixed ladder: a) Maintenance Shop, where employees were exposed to an eight foot fall when gaining access to the storage area located above the Clean Room.
Recent events (1)
- · Z (S) $0
1910.147 C04 I
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) Maintenance Shop, written procedures had not been developed where employees perform preventative maintenance and repairs on gasoline and diesel operated motor vehicles. The U.S. Army Corps of Engineers was previously cited for a violation of this standard which was contained in OSHA inspection no. 314899196, citation no. 2, item no. 1, issued on May 31, 2011 with respect to a workplace at Enumclaw, WA.
Recent events (1)
- · Z (R) $0
1910.213 B03
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.213(b)(3): Provisions were not made to prevent woodworking machine(s) from automatically restarting upon restoration of power after power failure: a) Maintenance Shop, where wood working machines not equipped with anti-restart devices included: 1. Jet Woodworking Band saw 2. Jet Belt Sander 3. Jet 6inch Bedworking Jointer 4. Delta 10 inch Unisaw The U.S. Army Corps of Engineers was previously cited for a violation of this standard which was contained in OSHA inspection no. 314899196, citation no. 1, item no. 3, issued on May 31, 2011 with respect to a workplace at Enumclaw, WA.
Recent events (1)
- · Z (R) $0
1910.302 B02
- Issued
- Apr 24, 2012
- Abate by
- Jun 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.302(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling: a) Electrical equipment not used as listed or labeled included: 1. Multi-Purpose Room, where a Network Surge Arrest relocatable power tap was daisy chained with a TSE relocatable power tap and used to supply power to computer equipment. (Item corrected) 2. Maintenance Shop, were a Tripp-Lite relocatable power tap was used to supply power to the Oregon Chainsaw Sharpener. 3. Maintenance Shop, were a relocatable power tap was used to supply power to the Jet Pedestal Grinder. The U.S. Army Corps of Engineers was previously cited for a violation of this standard which was contained in OSHA inspection no. 314899196, citation no. 2, item no. 5, issued on May 31, 2011 with respect to a workplace at Enumclaw, WA. The U.S. Army Corps of Engineers was previously cited for a violation of this standard which was contained in OSHA inspection no. 107965, citation no. 1, item no. 1, issued on October 26, 2011 with respect to a workplace at Federal Way, WA. The U.S. Army Corps of Engineers was previously cited for a violation of this standard which was contained in OSHA inspection no. 309096493, citation no. 2, item no. 1, issued on November 16, 2009 with respect to a workplace at Seattle, WA. The U.S. Army Corps of Engineers was previously cited for a violation of this standard which was contained in OSHA inspection no. 309092500, citation no. 1, item no. 5b, issued on October 12, 2007 with respect to a workplace at Burbank, WA.
Recent events (1)
- · Z (R) $0
More inspections at U.S. Army Corps of Engineers Howard Hanson DAM
View U.S. Army Corps of Engineers Howard Hanson DAM's full OSHA safety record →
More inspections in this industry (NAICS 921190)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 333290708.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.