Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BOWMAN CONSTRUCTORS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BOWMAN CONSTRUCTORS in 478 VAUGHN ROAD, DOVER FOXCROFT, ME 04426 (NAICS 236220). OSHA activity number 333292316.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bowman Constructors — free Get an email when a new federal OSHA severe-injury report for Bowman Constructors is published. One employer, no account, unsubscribe in one click.
Establishment
BOWMAN CONSTRUCTORS
Site address
478 VAUGHN ROAD
City
DOVER FOXCROFT
State
ME
ZIP
04426
Mailing
P.O. BOX 156, NEWPORT, ME 04953
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
6
Ownership type
A

3 citations on file for this inspection.

1926.404 B01 II

Serious Gravity 5 2 instances 2 exposed
Issued
Apr 18, 2012
Abate by
Apr 23, 2012
Penalty
Initial $1,870 · Current $1,300 Reduced
29 CFR 1926.404(b)(1)(ii):     All 120-volt, single-phase 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5kW, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, need not be protected with ground-fault circuit interrupters:    Dover Foxcroft Waste Water Treatment Plant - The pipe fusing machine, grinder, and extension cords were not protected by GFCIs.
Recent events (2)
  • — I (S) $1300
  • — Z (S) $1870

1926.651 J02

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 18, 2012
Penalty
Initial $1,496 · Current $1,040 Reduced
29 CFR 1926.651(j)(2):     Employees shall be protected from excavated or other materials or equipment that could pose a hazard by falling or rolling into excavations.  Protection shall be provided by placing and keeping such materials or equipment at least 2 feet (.61 m) from the edge of excavations, or by the use of retaining devices that are sufficient to prevent materials or equipment from falling or rolling into excavations, or by a combination of both if necessary:    Dover Foxcroft Waste Water Treatment Plant - The excavated material from the upper lagoon excavation was not positioned at least 2 feet from the edge of the trench.
Recent events (2)
  • — I (S) $1040
  • — Z (S) $1496

1926.405 G01 III C

Other-than-serious 2 instances 2 exposed
Issued
Apr 18, 2012
Abate by
Apr 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1926.405(g)(1)(iii)(C):   Flexible cords or cables were run through doorways, windows, or similar openings, except as permitted in paragraph(a)(2)(ii)(1) of this section:    Dover Foxcroft Waste Water Treatment Plant - The door of the Grit Building was not blocked or secured to prevent damage to the extension cords.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Bowman Constructors's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 333292316.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.