Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KEYSTONE MASONRY

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of KEYSTONE MASONRY in WT ADMINISTRATION BLD. JACKSON AVE, JOINT BASE LEWIS MCCHORD, WA 98433 (NAICS 238140). OSHA activity number 333883825.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Keystone Masonry — free Get an email when a new federal OSHA severe-injury report for Keystone Masonry is published. One employer, no account, unsubscribe in one click.
Establishment
KEYSTONE MASONRY
Site address
WT ADMINISTRATION BLD. JACKSON AVE
City
JOINT BASE LEWIS MCCHORD
State
WA
ZIP
98433
Mailing
P.O. BOX 2249, YELM, WA 98597
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238140
Employees
18
Ownership type
A

1 citation on file for this inspection.

1926.403 B02

Serious Gravity 5 1 instance 10 exposed
Issued
May 8, 2012
Penalty
Initial $3,213 · Current $1,607 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    (a)  Fort Lewis, Warrior In Transition Building, Keystone job trailer, Three relocatable power taps were plugged into each other daisy chained , which powered items including but not limited to: a task light, 12.8 amp Heater (model#90702G), Milwaukee battery chargers (for portable drills), and an extension cord which was used to power a 11.0 amp DeWalt Rotary Hammer (model no. D25550). The UL listing states that relocatable power taps are designed for indoor use and low amperage computer and audiovisual types of equipment, the load rating is 12.0 amps.   The UL listing also states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to electrical fire hazards.
Recent events (2)
  • — I (S) $1606.5
  • — Z (S) $3213

View Keystone Masonry's full OSHA safety record →