NORFOLK, VA —
OSHA Inspection: FURMANITE AMERICA INCORPORATED
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FURMANITE AMERICA INCORPORATED in 1447 WEST 27TH STREET, NORFOLK, VA 23508 (NAICS 336611). OSHA activity number 333885820.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FURMANITE AMERICA INCORPORATED
- Site address
- 1447 WEST 27TH STREET
- City
- NORFOLK
- State
- VA
- ZIP
- 23508
- Mailing
- 101 OLD UNDERWOOD ROAD BLDG E, LA PORTE, TX 77571
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336611
- Employees
- 12
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.303 G02 I
- Issued
- May 18, 2012
- Penalty
- Initial $3,400 · Current $2,550 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means: a.) Furmanite America Inc., Shop Area, Electrical Panel #4. On or about April 12, 2012, the blank cover over breaker #9 did not fully enclose the opening, leaving a gap and exposing employees to inadvertent contact with the energized busbar in the rear of the panel box.
Recent events (2)
- — I (S) $2550
- — Z (S) $3400
1910.305 B01 II
- Issued
- May 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. a.) Furmanite America Inc., Shop Area, metal junction box mounted on the wall near Baldor pedestal grinder. On or about April 12, 2012, the junction box housing the service wiring leading to the grinder, had an unused opening in that the knockout plug was missing exposing employees to inadvertent contact with live parts. b). Furmanite America Inc., Valve Storage Room, Lapmaster 12 - lubricating machine. On or about April 12, 2012, employees were exposed to live parts in that openings were not fully enclosed where the flexible cord entered the machine exposing the connection to the operating switch.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- May 18, 2012
- Penalty
- Initial $2,550 · Current $1,913 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. a.) Furmanite America Inc., Shop Coordinator's Office. On or about April 12, 2012 the VG307 multi-receptacle surge protector in use was not properly grounded.
Recent events (2)
- — I (S) $1912.5
- — Z (S) $2550
1915.87 E
- Issued
- May 18, 2012
- Penalty
- Initial $2,550 · Current $1,913 Reduced
General-duty citation text
29 CFR 1915.87(e): Where the potential exists for an employee to be splashed with a substance that may result in an acute or serious injury, the employer shall provide facilities for quick-drenching or flushing of the eyes and body. a.) Furmanite America Inc., Boiler Room, Valve flushing area, Bradley shower/eye wash unit. On or about April 12, 2012, the employer did not ensure the shower/eye wash unit available for use by employees was in good working order, in that the unit had not been maintained or flushed as evidenced by the dust/debris covering the nozzles and the bowl.
Recent events (2)
- — I (S) $1912.5
- — Z (S) $2550
1910.303 B02
- Issued
- May 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. a.) Furmanite American Inc., Shop Coordinator's Office. On or about April 12, 2012, the VG307 multi-receptacle surge protector was not used as to its listed and labeled purpose in that a portable electric fan was plugged into the unit.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 II
- Issued
- May 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a.) Furmanite America Inc., Shop Area. On or about April 12, 2012 the working space in front of the facility's main electrical panels, circuit breaker panels, and equipment disconnect switches was used for storage in that miscellaneous items such as, but not limited to pallets loaded with various-sized valves, a welding machine, and large boxes were located within 17 inches of the working space.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 F05 I
- Issued
- May 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(5)(i) as referenced in 29 CFR 1915.1200: The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein: a.) Furmanite American Inc., Shop Area, work bench flammable storage cabinet. On or about April 12, 2012, a one quart plastic spray bottle containing an unknown liquid was not labeled as to its contents.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 F05 II
- Issued
- May 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(5)(ii) as referenced in 29 CFR 1915.1200: The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the appropriate hazard warnings: a.) Furmanite American Inc., Shop Area, work bench flammable storage cabinet. On or about April 12, 2012, a one quart plastic spray bottle containing an unknown liquid was not labeled as to the chemical or physical hazards associated with the use of the contents within.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1915.81 A03
- Issued
- May 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1915.81(a)(3): The employer shall store materials in a manner that does not create a hazard for employees. 29 CFR 1915.81(a)(3): The employer shall store materials in a manner that does not create a hazard for employees. a.) Furmanite America Inc., workbench flammable storage locker. On or about April 12, 2012, items stored in the flammable storage locker were not properly stored in accordance with the material safety data sheet, in that several one-quart containers of Fel-pro Clover Compound, and Timesaver Lapping Compound did not have lids covering the contents.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1915.134 B
- Issued
- May 18, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1915.134(b): Work rests were not kept a distance not to exceed 1/8 inch from the surface of the wheel. a.) Furmanite America Inc., Shop Area., Baldor Pedestal Grinder, Serial No. N.PD107, Lot No. 125W, 3 phase, 1500/1800 rpm. On or about April 12, 2012 the work rest was improperly adjusted to 1/2" from the rotating wheel.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 336611)
More inspections in VA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 333885820.